background image

3

Product description

3.1

Product characteristics

The device is an interface coupler, which can be used to connect connected devices
(e.g. WLL180T) to a PROFINET IO network. The relevant devices are connected via a
simple plug system on the side of the coupler.

Usually, the entire system is mounted on a mounting rail close to the application.

The coupler supports up to 16 connected devices, which are likewise connected to one
another via the plug system.

Further properties:

PROFINET IO device

Option to communicate via function block (e.g. Siemens SFB52 or SFB53)

2 Ethernet ports with transmission speed of 10 or 100 MBaud

Further specifications can be found in the technical data (

see "Technical data",

page 31

).

3.2

Setup and function

1
2

3

6

5

4

1

Bus male connector (system bus)

2

Service port

3

Power supply connection (M8), 4-pin

4

D-coded M12 connector, 4-pin, PROFINET / Ethernet

5

D-coded M12 connector, 4-pin, PROFINET / Ethernet

6

Status LEDs

3.3

Interfaces

3.3.1

PROFINET

1

4

3

2

Table 2: PROFINET pin assignment

Pin

Pin assignment

1

Tx+

2

Rx+

PRODUCT DESCRIPTION

8

O P E R A T I N G   I N S T R U C T I O N | WI180C-PN

8023551/11HP/2019-03-07 | SICK

Subject to change without notice

Summary of Contents for 6068088

Page 1: ...O P E R A T I N G I N S T R U C T I O N WI180C PN WI180C PN PROFINET coupler ...

Page 2: ...n the limits of the legal determination of Copyright Law Any modifica tion abridgment or translation of this document is prohibited without the express writ ten permission of SICK AG The trademarks stated in this document are the property of their respective owner SICK AG All rights reserved Original document This document is an original document of SICK AG 2006 42 EC NO SAFETY 2 O P E R A T I N G...

Page 3: ...ransport and storage 10 4 1 Transport 10 4 2 Storage 10 5 Mounting 11 5 1 Required materials 11 5 2 Preparing mounting location 11 5 3 Scope of delivery 11 5 4 Mounting procedure 11 5 5 Connecting the device 12 6 Commissioning 13 6 1 Configuration 13 6 2 Switching on 13 7 Operation 14 7 1 Safety 14 7 2 Daily thorough check 14 7 3 LED status indicators 14 7 4 Device slots and modules 15 7 5 Cyclic ...

Page 4: ... Disposal 30 10 Technical data 31 10 1 Dimensional drawings 31 10 2 Technical data 31 10 3 Ordering information accessories 33 11 UL Satisfaction Ratings 34 CONTENTS 4 O P E R A T I N G I N S T R U C T I O N WI180C PN 8023551 11HP 2019 03 07 SICK Subject to change without notice ...

Page 5: ...o the device Product description Mounting Electrical installation Commissioning and configuration Furthermore when planning and using sensors such as the device technical expertise is required which is not covered in this document Official and legal regulations for operating the device volume measurement system must always be complied with You can find further information on the Internet at www si...

Page 6: ... information Table 1 Product information Product name WI180C PN Article number 6068088 Device version PROFINET Manufacturer SICK AG 1 6 Further information www sick com The following information is available on the Internet Other language versions Data sheets and application examples CAD data of drawings and dimensional drawings Certificates e g EU declaration of conformity Current device files 1 ...

Page 7: ... set parameters Only operate the device within the set operating parameters Regularly check that the device is functioning properly Structural modifications to the device are not permitted The device is not designed as a safety product This device complies with the Radio Safety Requirements EMC for the industrial sector Radio Safety Class A It may cause radio interference if used in a residen tial...

Page 8: ...device Option to communicate via function block e g Siemens SFB52 or SFB53 2 Ethernet ports with transmission speed of 10 or 100 MBaud Further specifications can be found in the technical data see Technical data page 31 3 2 Setup and function 1 2 3 6 5 4 1 Bus male connector system bus 2 Service port 3 Power supply connection M8 4 pin 4 D coded M12 connector 4 pin PROFINET Ethernet 5 D coded M12 c...

Page 9: ... Pin Pin assignment 1 12 24 VDC 2 Not assigned 3 GND 4 Not assigned 3 3 3 Grounding The device is grounded via the mounting rail by means of a spring contact PRODUCT DESCRIPTION 3 8023551 11HP 2019 03 07 SICK O P E R A T I N G I N S T R U C T I O N WI180C PN 9 Subject to change without notice ...

Page 10: ...ondi tions see Technical data page 31 4 2 Storage If you want to store the devicefor a relatively long time pack it as you would for trans port Make sure that the storage location complies with the permitted environmental conditions see Technical data page 31 4 TRANSPORT AND STORAGE 10 O P E R A T I N G I N S T R U C T I O N WI180C PN 8023551 11HP 2019 03 07 SICK Subject to change without notice ...

Page 11: ...unting rail in the same area as the application 2 Lay the two pre assembled cables so that they can easily be connected to the con nections of the device If necessary use cable channels cable ties and cable grips 5 3 Scope of delivery WI180C PN Quick start instructions 5 4 Mounting procedure 1 Carefully unpack the device 1 2 2 Clamp the device onto the mounting rail as shown in the image 3 Clamp t...

Page 12: ...2 the male M12 D coded connector for the PROFINET network to the PROFINET connection on the device and secure it using the sleeve nut 2 Connect the female M8 connector on the power supply to the underside of the device and screw the male connector tight 1 see the operating instructions for the relevant device 2 AOD1 devices on left side of WI180C PN WLL180T devices on left side of AOD 5 MOUNTING 1...

Page 13: ...d the current GSD file for the device from www sick com 3 Install the GSD file in your engineering tool 6 2 Switching on 1 Switch on the power supply for the device 2 Wait approximately two seconds until the device indicates that it is ready see LED status indicators COMMISSIONING 6 8023551 11HP 2019 03 07 SICK O P E R A T I N G I N S T R U C T I O N WI180C PN 13 Subject to change without notice ...

Page 14: ...ation with each of the con nected devices 7 3 LED status indicators Table 4 LED status indicators LED Indication Meaning PWR green Power on dark Power off BF Bus fault dark PROFINET connection ok red Device offline from PROFINET red blinking PROFINET communication start up or invalid config uration SF System fault dark PROFINET connection ok red System fault of the device STATUS dark Device not co...

Page 15: ...180T F Fiber amplifier expansion unit WLL180T base unit can only be placed as module 2 16 No extra power supply to WLL180T device required OD1 on one input of AOD1 M Displacement sensor evaluation base unit For each AOD1 unit plugged the total number of pluggable modules decreases by one max 8 AOD1 units possible If AOD1 and WLL180T are used in combination with WI180C PN all WLL180T devices must b...

Page 16: ...ule 2 16 No extra power supply to KTL180 device required 7 5 Cyclic communication via PROFINET IO The following modules are supported by WI180C PN Table 6 Supported modules Module Module Ident No Applicable slot Data direction Byte address Function 1 0x0101 1 Input and Output In 0 7 Out 0 3 All binary module inputs and outputs with global configura tion settings 2 0x0102 1 default mode Input and O...

Page 17: ... Unsigned 16 bit value Measurement value 1 Input 4 Depending on module 0 Unsigned 16 bit value Measurement value 1 Input 5 Depending on module 0 Unsigned 16 bit value Measurement value 1 Input 6 Depending on module 0 Unsigned 16 bit value Measurement value 1 Input 7 Depending on module 0 Unsigned 16 bit value Measurement value 1 Input 8 Depending on module 0 Unsigned 16 bit value Measurement value...

Page 18: ...00 Global configuration Byte 0 record major version number read only Byte 1 record minor version number read only Byte 2 3 global configuration settings b1 global diagnostics disable enable R W 4 Version number 1 0 0x01 0x00 Global diagnostics 0 disable 1 enable default 7 9 Record data NOTE Each module has 256 unique record addresses Slot 1 Gateway Records 0x2000 0x20FF Slot 2 Sensor 1 left most R...

Page 19: ...A Find me R W 2 0 Stop 1 Start 0x20D4 Factory reset R 2 3 Execute Module WLL180T 0xnn00 Products series b15 12 Manufacturer b11 8 Categories b7 0 Family R 2 0x1101 1 output model 0x1102 2 outputs model 1 SICK 1 Fiber amplifier 1 WLL180T 1 output 2 WLL180T 2 outputs 0xnn01 Product type R 2 17 WLL180T 0xnn02 Firmware version R 2 0x0200 or higher 0xnn03 Protocol version R 2 1 0xnn04 Product Revision ...

Page 20: ...H1 Lower limit R W 2 999 9999 Any value out of range will be replaced by the nearest valid value 0xnn6F CH1 Upper limit 2 0xnn70 CH2 Lower limit 2 0xnn71 CH2 Upper limit 2 0xnn72 Timer setting CH1 R W 2 0 Off delay 1 One shot 0xnn73 CH2 2 0xnn74 Off delay time CH1 R W 2 0 9999 0 9999 ms 1 9 0 1 0 9 ms 0xnn75 On delay time CH1 2 0xnn76 Off delay time CH2 2 0xnn77 On delay time CH2 2 0xnn7B Hysteres...

Page 21: ...uct type name 0xnn07 Product ID User R 2 16 Actual product type code 0xnn08 Tag name R W 2 32 Blank space default 0xnn09 Operation Status R 2 0 Init 1 Idle 2 Run 3 In operation by user 0xnn62 Error code R W 2 Read last error code Write any value delete last error code AOD1 parameters applied to both connected sensors 0xnn64 Threshold Near R W 2 32768 32767 default 50 0xnn65 Far R W 2 32768 32767 d...

Page 22: ...00 0xnn78 Analog scaling min 0V 4mA R W 2 32768 32767 default 10000 0xnn81 Amplifier infor mation b15 b0 Amplifier product series R 2 0x1503 AOD1 parameters applied to sensor in this slot only 0xnn67 Calculation flags R W 2 0 No calculation 1 Calculation 0xnn68 Calculation coef ficient A Add R W 2 10000 10000 default 0 0xnn69 Calculation coef ficient M Multiply R W 2 10000 10000 default 1 0xnn6A C...

Page 23: ... 2000 us 3 4000 us 4 Auto 0xnn89 Key lock R W 2 0 Unlocked 1 Locked 0xnn8A Switching behav ior R W 2 0 Light ON 1 Dark ON 0xnn8B Near end calibra tion R W 2 OD1 15 mm 7499 7499 default 5000 OD1 35 mm 2249 2249 default 1500 OD1 100 mm 7499 7499 default 5000 0xnn8C Far end calibra tion R W 2 OD1 15 mm 7499 7499 default 5000 OD1 35 mm 2249 2249 default 1500 OD1 100 mm 7499 7499 default 5000 0xnn8D Er...

Page 24: ...es b7 0 Family R 2 0x1321 1 SICK 3 Displacement 21 OL1 0xnn01 Product type R 2 17 0xnn02 Firmware version R 2 0x1011 0xnn03 Protocol version R 2 0 0xnn04 Product Revision R 2 0 0xnn05 Vendor name R 2 16 SICK AG 0xnn06 Product name R 2 32 Actual product type name 0xnn07 Product ID R 2 16 Actual product type code 0xnn08 User Tag name R W 2 32 Blank space default 0xnn09 Operation Status R 2 0 Init 1 ...

Page 25: ...nn75 Analog output selection R W 2 0 Off 1 Calculated 2 Head 1 3 Head 2 0xnn76 Analog scaling R W 2 0 Off 1 On 0xnn77 Analog scaling max 10 V 20 mA R W 2 32768 32767 default 10000 0xnn78 Analog scaling min 0 V 4 mA R W 2 32768 32767 default 10000 0xnn81 Amplifier infor mation b15 b0 Amplifier product series R 2 0x1503 AOD1 parameters applied to sensor in this slot only 0xnn67 Calculation flags R W...

Page 26: ...djusted 0xnnC8 Store zero reset W 2 0xnnC9 Cancel zero reset W 2 0xnnD4 Factory reset W 2 3 Execute All settings except Baud rate are reset to defaults Module KTL180 0xnn00 Products series b15 12 Manufacturer b11 8 Categories b7 0 Family R 2 0x1111 1 output model 0x1112 2 outputs model 1 SICK 1 Fiber amplifier 11 KTL180 1 output 12 KTL180 2 outputs 0xnn01 Product type R 2 17 WLL180T 0xnn02 Firmwar...

Page 27: ...ck 2 Lock but the external teach is available 0xnn6C Operation mode CH1 R W 2 0 Auto 1 Light on 2 Dark on 0xnn6D CH2 0xnn6E Threshold level CH1 Lower limit R W 2 999 9999 Any value out of range will be replaced by the nearest valid value 0xnn6F CH2 Upper limit 0xnn70 CH2 Lower limit 0xnn71 CH2 Upper limit 0xnn72 Timer setting CH1 R W 2 0 Off delay 1 One shot 0xnn73 CH2 0xnn74 Off delay time CH1 R ...

Page 28: ...l zero reset W 2 Write any value to execute Zero reset 0xnnCA Teach in 1 point W 2 1 CH1 2 CH2 0xnnCB Teach in 2 point W 2 0xnnD2 Reset W 2 3 Execute 0xnnD3 Return to Top Menu W 2 Write any value to go back to Top Menu 0xnnD4 Factory reset W 2 3 Execute Not available for locked unit 7 OPERATION 28 O P E R A T I N G I N S T R U C T I O N WI180C PN 8023551 11HP 2019 03 07 SICK Subject to change with...

Page 29: ...xtended error type Error text 19 WI180 system communication error 19 6 Number of modules in WI180 system changed 19 7 Invalid module in WI180 system 19 11 WI180 system internal communication error DIAGNOSIS 8 8023551 11HP 2019 03 07 SICK O P E R A T I N G I N S T R U C T I O N WI180C PN 29 Subject to change without notice ...

Page 30: ...es from the bus male connector of the device 5 Carefully push up the device until you can tip it forwards 2 1 6 Remove the device from the mounting rail 9 2 Disposal At the end of its service life the device must be disposed of correctly as waste electron ics Take the regulations in your country into account also 9 DECOMMISSIONING 30 O P E R A T I N G I N S T R U C T I O N WI180C PN 8023551 11HP 2...

Page 31: ... pin system bus 9 D coded M12 connector 4 pin PROFINET Ethernet ß D coded M12 connector 4 pin PROFINET Ethernet à Factory reset button á Service port USB Micro B â M12 Connector Cap accessory 10 2 Technical data Electrical Table 11 Electrical data Description Value Supply voltage 12 24 VDC 10 Power consumption with out connected devices 3 W Switch on delay 1000 ms Switch on delay overall system 20...

Page 32: ...rmance class Class C PROFINET IRT Netload class III Ethernet ports 2 PROFINET features Media Redundancy MRP network diagnostic MIB SNMP topology detection port diagnostic Up Down connection diagnostic connection length measurement I M0 4 auto device replacement reduction ratio openVAS tested GSD file available V2 2 V2 32 V2 33 V2 34 EMC Table 13 EMC data Description Value Noise immunity Length of ...

Page 33: ... range Operation 8 connected devices 25 50 C 1 Temperature range Operation 16 connected devices 25 45 C 1 1 Temperature ranges valid if no output current on connected devices 10 3 Ordering information accessories Table 17 Ordering information Type Description Part number YF8U14 020VA3XLEAX Female connector M8 4 pin straight 2 m cable 2095888 YF8U14 050VA3XLEAX Female connector M8 4 pin straight 5 ...

Page 34: ...t 12 24 V dc max 0 45 A Class 2 Maximum surround air Temperature 55 C Up to 8 units Input 12 24 V dc max 1 02 A Class 2 Output 12 24 V dc max 0 8 A Class 2 Maximum surround air Temperature 50 C Up to 16 units Input 12 24 V dc max 1 02 A Class 2 Output 12 24 V dc max 0 8 A Class 2 Maximum surround air Temperature 45 C 11 UL SATISFACTION RATINGS 34 O P E R A T I N G I N S T R U C T I O N WI180C PN 8...

Page 35: ...UL SATISFACTION RATINGS 11 8023551 11HP 2019 03 07 SICK O P E R A T I N G I N S T R U C T I O N WI180C PN 35 Subject to change without notice ...

Page 36: ...Mexico Phone 52 472 748 9451 E Mail mario garcia sick com Netherlands Phone 31 30 2044 000 E Mail info sick nl New Zealand Phone 64 9 415 0459 0800 222 278 tollfree E Mail sales sick co nz Norway Phone 47 67 81 50 00 E Mail sick sick no Poland Phone 48 22 539 41 00 E Mail info sick pl Romania Phone 40 356 171 120 E Mail office sick ro Russia Phone 7 495 775 05 30 E Mail info sick ru Singapore Phon...

Reviews: