VM-704 TEMPERATURE
MONITOR MODULE
Page 2 of 4
VM-7 SERIES
SPECIFICATION
30904E1.3
Issued Feb.
2009
Revised Mar. 2010
CONTACT
Contact (RELAY1) : OR (DANGER-1 / DANGER-2 / DANGER-3)
Contact (RELAY2) : OR (ALERT-1 / ALERT-2 / ALERT-3)
Contact (RELAY3) : OR (NOT-OK-1 / NOT-OK-2 / NOT-OK-3)
Contact (RELAY4) : OR (DANGER-4 / DANGER-5 / DANGER-6)
Contact (RELAY5) : OR (ALERT-4 / ALERT-5 / ALERT-6)
Contact (RELAY6) : OR (NOT-OK-4 / NOT-OK-5 / NOT-OK-6)
Contact Mode
: Normally de-energized
OTHERS
Initial low alarm bypass
: OFF
Fast out
: OFF
Timed OK channel defeat : ON
Burnout :
Downscale
0%
INPUT
Input points
:
6ch
Input transducer
:
100
Ω
3-wire RTD (R100/R0=1.3851)
Monitor range
:
0 to 200°C
RECORDER OUTPUT
Output range
:
4 to 20mA
(4mA at the burnout)
ALARM
H-DANGER set point
:
160°C
H-ALERT set point
:
120°C
L-ALERT set point
:
None
L-DANGER set point
:
None
Alarm delay time
:
3 sec (DANGER, ALERT)
Alarm reset
:
AUTO-RESET
Alarm contact operation
Monitor power ON
Monitor alarm relay mode
Monitor power OFF
Normal state
Alarm state
NO contact (NORMALLY DE-ENERGIZED)
OPEN
OPEN
CLOSE
NO contact (NORMALLY ENERGIZED)
OPEN
CLOSE
OPEN
NO contact (NORMALLY DE-ENERGIZED)
CLOSE
CLOSE
OPEN
NC contact (NORMALLY ENERGIZED)
CLOSE
OPEN
CLOSE
Default Value