VM-701 VIBRATION / DISPLACEMENT
MONITOR MODULE
Page 2 of 4
VM-7 SERIES
SPECIFICATIONS
30901E1.3
Issued Feb.
2009
Revised Jun. 2010
ACCESSORY SPECIFICATION CODE / IDENTIFIED BY TB
□
Code Accessory
Quantity (Part Code)
/TB1 Transducer input terminal plug (15-pin)
FRONT-MC-1.5/15-STF-3.81(Phoenix Contact) : 2pieces (7072NAB)
Note2)
Recorderr output terminal plug (6-pin)
FRONT-MC-1.5/6-STF-3.81(Phoenix Contact) : 2pieces (7072NAC)
Note2)
Contact output terminal plug (18-pin)
FRONT-MC-1.5/18-STF-3.81
(Phoenix Contact) : 1piece (7072NAA)
/TB2 Contact output terminal plug (18-pin)
FRONT-MC-1.5/18-STF-3.81
(Phoenix Contact) : 1piece (7072NAA)
Note1) D-sub plugs and hoods are not included in this code. Please make
necessary arrangement seperately, if required.
Note2) When individually ordering specify the parts code,it is require to arrange
for a necessary amount.
Specification
ENVIRONMENTAL CONDITION
Operating temperature : 0 to +65°C
Storage temperature
: -30 to +85°C
Relative humidity
: 20 to 95%RH (noncondensing)
POWER CONSUMPTION
Module
: Less than 15W
MATERIAL AND FINISH
Face plate
: ABS (Black)
Sheet
: Polyester tough top (Gray)
Base plate
: Alminium alloy (Silver)
MASS
Body
: Max. 1.0kg (2.2lb)
Alarm contact operation
Monitor power ON
Monitor alarm relay mode
Monitor power OFF
Normal state
Alarm state
NO contact (NORMALLY DE-ENERGIZED)
OPEN
OPEN
CLOSE
NO contact (NORMALLY ENERGIZED)
OPEN
CLOSE
OPEN
NC contact (NORMALLY DE-ENERGIZED)
CLOSE
CLOSE
OPEN
NC contact (NORMALLY ENERGIZED)
CLOSE
OPEN
CLOSE
Default value
INPUT
Monitoring
: Displacement input vibration monitor
Monitor range
: 0 to 100 µm pk-pk
Input transducer
: FK-202F (non-intrinsic safety)
Input points
: 4 points
Input impedance
: 50k
Ω
FILTERING
Low cut-off frequency : 5Hz (4
th
-order)
High cut-off frequency : 4kHz
RECORDER OUTPUT
Output range
: 4 to 20mA
(4mA at the burnout)
Alarm
DANGER set point : 80µm
ALERT set point
: 60µm
OK set point
: -1.4V (Low), -18.8V (High)
Alarm delay time
: 3sec (DANGER, ALERT)
Alarm reset
: AUTO-RESET
CONTACT OUTPUT
Contact (RELAY1) : OR logic (DANGER-1 / DANGER-2)
Contact (RELAY2) : OR logic (ALERT-1 / ALERT-2)
Contact (RELAY3) : OR logic (NOT-OK-1 / NOT-OK-2)
Contact (RELAY4) : OR logic (DANGER-3 / DANGER-4)
Contact (RELAY5) : OR logic (ALERT-3 / ALERT-4)
Contact (RELAY6) : OR logic (NOT-OK-3 / NOT-OK-4)
Contact Mode
: Nomally de-energized
OTHERS
Sequnce set value
: 1
Suppression set value
: 0%
Fast out
: OFF
Timed OK channel defeat : ON
Burnout :
Downscale
0%