VM-703 TACHOMETER & ECCENTRICITY
MONITOR MODULE
Page 1 of 5
VM-7 SERIES
SPECIFICATIONS
30903E1.2
Issued Feb.
2009
Revised Mar. 2010
Non-incendive *
1
Custom set up
Tropical spec.
I/O terminal block for:
1
Class I Division 2 CSA
1 VM-761 instrument rack
2 VM-762 instrument rack
*1
In future
INPUT
Input points (tachometer) : Max. 2 ch
Input points (eccentricity) : Max. 1 ch
Input impedance
: Approx. 50k
Ω
(Magnetic pickup input : Approx. 5k
Ω
)
Max input voltage range : 100Vp-p
Hysterics set value
: 1V, 2V, 5V
INPUT TRANSDUCER for TACHOMETER
(Only Channel 1 and Channel 2)
Proximity transducer
: FK-202F, RD-05A
Magnetic pickup
: MS-160, MS-240
Input block
: 1ch and/or 2ch circuit
INPUT TRANSDUCER for ECCENTRICITY (Only Channel 3)
Proximity transducer
: FK-202F, VK-202A, VK-202P, VK-302P
VC-020
Input block
: 3ch circuit
OUTPUT
Indicators
: OK LED (Green)
TRG LED (Yellow)
Monitor output
: Input signal is output via a buffer amplifier.
Location
: Front panel and rear panel
Output impedance
: Approx. 100
Ω
(Max. 0.5mA)
Pulse output
: Shaped pulse signal is output via a buffer amplifier.
Location
: Front panel and rear panel
Output impedance
: Approx. 1k
Ω
(Max. 0.5mA)
Signal level
: 0V (V
OL
), 5V (V
OH
)
Recorder output : Voltage or current output proportional monitor range.
Output range
: 1 to 5VDC, 4 to 20mADC
0 to 5VDC, 0 to 10VDC
I/O conversion accuracy:
±1% of F.S. at 25°C*
2
±2% of F.S. at 0°C to 65°C*
2
Max. load resistance : 600
Ω
(current mode)
Output impedance
: Approx. 500
Ω
(voltage mode)
Insulation resistance : 10M
Ω
at 100VAC
Burnout function
: Downscale 0%
Downscale 0mA / 0mV
Transducer power supply:
Proximity transducer : -24VDC / 25mA Max.
Alarm contact
:
Number of relay
: 6 points (logic changeable)
Contact type
: Dry contact (SPDT)
Contact capacity
: 250VAC / 5A, 30VDC / 5A
Note) *2
At calibrate frequency.
SPEED RELAY (Only Channel 1 and Channel 2)
Speed relay set point
: 4 points (HH, H, L, LL), from 0.1rpm to 100% of
monitor range, field changeable.
Speed relay hysterics
: 0 to 100 rpm (1 rpm step, field changeable)
Speed relay mode
: Over speed / Under speed
Speed relay set accuracy : ±1 digit or less (on digital indicator)
Relay reset
: AUTO-RESET / SELF-HOLD
Relay contact mode
: Normally de-energized / Normally energized
ALARM (Only Channel 3)
Alarm set point
: Eccentricity (P-P) monitoring
2 points (DANGER, ALERT),
from 0 to 100% of monitor range, field changeable
Eccentricity (Direct) monitoring
4
points
(H-DANGER, H-ALERT, L-DANGER, L-ALERT),
from 0 to 100% of monitor range, field changeable
Alarm set accuracy
: ±(0.2% of F.S.+1digit) or less at 25°C
Alarm set repeat
: ±1digit or less at 25°C
Alarm delay time
: 0.5, 1 to 99 sec (1sec step, field changeable)
Alarm reset
: AUTO-RESET or SELF-HOLD field changeable.
Alarm contact mode
: Normally de-energized / Normally energized
Alarm bypass function : Block off alarm output (DANGER)
TACHOMETER
Min. pulse width
: 50µsec
Min. measured frequency : 0.01Hz
Max. measured frequency : 10 kHz
Input voltage
: Less than 100V p-p
ROTOR SPEED MONITORING
Accuracy
: ±(0.003% of rdg. +1digit) at 25°C
±(0.03% of rdg. +1digit) at 0°C to 65°C
Min. indicated frequent
: Lower of 1Hz or under speed setting.
No. of input pulse
: 1 to 200 pulse / rev.
ROTOR ACCELERATION MONITORING
Accuracy
: ±20 digit at 0 to 65°C
No. of input pulse
: 1 to 200 pulse / rev.
(60 or 120 pulse / rev. is recommended.)
REVERSE ROTATING MONITORING
Accuracy
: ±(0.003% of rdg. +1digit) at 25°C
±(0.03% of rdg. +1digit) at 0°C to 65°C
Min. indicated frequent
: Lower of 1Hz or under speed setting.
No. of input pulse
: 1 to 60 pulse / rev.
Note)
The angle between the sensors shall be
as follows :
θ
s=(90+360n)/Z
[n=0,1,2,3•••, Z:Numbers of the teeth]
θ
s is recommended to be within 90 to
270° and to satisfy the above equation.
ECCENTRICITY MONITORING
Phasemarker
: Selection from three kinds
Ch1 input ,
Phasemarker 1 (from VM-741 PhaseMarker)
Phasemarker 2 (from VM-741 PhaseMarker)
P-P Monitoring
: Accuracy
: ±1% of F.S. at 25°C*
2
±2% of F.S. at 0°C to 65°C*
2
Measure range
: 1 to 300rpm, 1 to 600rpm
Output block
: 3ch circuit
Direct Monitoring : Accuracy
: ±1% of F.S. at 25°C
±2% of F.S. at 0°C to 65°C
Measure range
: 1Hz or less.
Zero shift function : -50 to +50% of the monitor range.
Output block
: 4ch circuit
Note) *2
At calibrate frequency.
Specification
Model Code / Additional Spec. Code ( )
No entry if additional
spec, code is not specified.
VM-703 /NB1 /CSU /TRP /TB
Forward
direction
Sensor for CH2
Sensor for CH1
θ
s