(2) Operation Check
WARNING : ELECTRIC SHOCK
Before turning the circuit breaker to ON position, ensure that the breaker or the
switch of loads are positioned to OFF.
Operate the circuit breaker, well-communicating with the electrician by the load
side.
Before operating the generator, check always
if the device can work.
●
Actuation test of the Earth Leakage Relay and Breaker
Ensure that the breaker and the switches
of loads are positioned to OFF.
Ensure that the circuit breaker
positioned to OFF.
Following the procedure in 9-1,
Initial Starup / Pre-Check,start an engine.
Turn (Push-up) the circuit breaker (lever)
to ON position.
Push the test button in the earth leakage relay unit.
When the button is pushed, the earth leakage indicating
lamp turns ON and circuit breakers are positioned in the
middle between ON and OFF positions simultaneously,
the device works normally
Push the reset button. The earth leakage indicating lamp turns OFF
subsequently.
Turn (Push-down) the circuit breaker (lever) to OFF position.
In the event you cannot complete every step of the above procedure to the end,
the device is out of order. Consult with our authorized distributor or our
engineering section and ask to repair.
1
3
2
4
5
6
7
Battery Isolator
Circuit Breaker
RESET Button
TEST Button
Earth Leakage Relay
Earth Leakage Relay