< NOTE >
Do not continuously operate the starter motor for 10 sec. or more.
If repeating starter switch operation, wait 30 sec. or more between operating.
Be aware that smoke might be generated when the engine is started.
After starting the engine, remove your hand from the starter switch.
The engine idles for approximately five minutes.
Turn the Throttle Lever to <RUN>.
Ensure that the tachometer shows the following frequency at no load.
No Load Frequency (Revolving Speed)
50Hz RUN
52.5Hz (about) (1575min
-1
)
Adjust the voltage regulator dial to the specified voltage.
50Hz RUN
415V
Turn the breakers to ON to start power transmission.
WARNING : ELECTRIC SHOCK
/
/
/
/
INJURY
Before turning the circuit breaker to ON position,ensure that the breaker or
the Switch of loads are positioned to OFF.
Operate the circuit breaker, well-communicating with the electrician by the
load side.
Battery Isolator
Circuit Breaker
Starter Switch
Preheat Lamp
Voltage Regulator
Throttle Lever
5
6
7
8
9
RUN
START POSITION
DECREASE
INCREASE
FREQUENCY ADJUST
THROTTLE
Throttle Lever
Frequency Adjusting Screw
Fixing Screw Nut