23
(3) The earth leakage breaker relay has activated
In the event the earth leakage breaker relay has activated, the earth leakage
indicating lamp Turns ON and the Circuit breaker (lever) trips off to be positioned in
the middle between ON and OFF positions.
In the above condition, even though you stop the engine once and start it again, the
Circuit breaker (lever) does not restore to ON or OFF, and the reset button does not
function, because the device keeps detecting current leakage.
Stop the engine promptly and find the leakage point to repair. After repairing the
leakage point(s), proceed with the following restoration steps. (In the case the earth
leakage indicating lamp does not turn to ON simultaneously, the cause is
Over-Loaded or Short-Circuit.)
Push the reset button or stop the engine.
Restore (Push-down) the Circuit breaker (lever) to OFF position.
By the above procedure, you can reset the Circuit breaker to ON positions.
1
2