10
Figure 3-5 linkage unit function zone
If the key switch of the system is allowed, press START to enable corresponding control
panels of the bus switched in, and meanwhile the indicator light is lit. On the contrary, press
STOP to disable corresponding control panels of the bus switched in.
The "FDBK" indicator light will be lit when the feedback signal access(For example,1-2 and
1-3 short-circuit).
The "FAULT" indicator light will be lit when the lines have problems.
Restart and login the system when the address is changed.
⑤
Manual module panel
Each manual panel has 12 manual control buttons, each button corresponds to a control
module. Button pressed completes start/stop of control module.Meanwhile the indicator light
will be lit.The binary address can be changed by these jumpers ranged from JP1 to JP4 of
manual panel. The address range of manual panel is as follows:
Starting address = address*30+1
Last address = address*30+12
The controller panel of manual panel including 12 controlled outputs is as follows:
Figure 3-6 manual panel function zone
If MANUAL CONTROL of the system is allowed, press
to enable corresponding control
panels of the bus switched in,and meanwhile the indicator light is lit. On the contrary, press
the button again to disable corresponding control panels of the bus switched in.The "FDBK"
indicator light will be lit when the feedback signal access.
Display interface of the screen: