"fire pump" as the output result, after that, the linkage relation is completely set. The system
supports complex linkage of any 99 points at most.
A complete linkage condition must include the following element:
12) Complete zone condition (for example, the room linage must include start room
number and end room number)
13) Type condition (that is, at least one equipment of a certain type is checked)
14) Delay time
15) Output result (that is, at least one module is requested for action when the condition
is satisfied)
If the user input these elements incorrectly during setup, the system will deny and present
corresponding prompt when OK button is pressed.
For secondary trigger of linkage:
Two equipment types will be triggered secondarily according to actual application
requirements of the system:
Far sound equipment
Note: The so-called "secondary trigger" means that when an activated module is
stopped manually and the linkage condition is satisfied again due to new fire alarm,
the module is requested for the second time.
The setup of other linkage types in the system is identical to that of system
linkage. The difference is the input box for other information is added in the linkage
condition setup. The following section gives a brief description based on the
illustration.
4.3.2
Zone linkage setup
The drop-down selection box is incorporated into the zone linkage. The corresponding
options will be displayed only after zone information is registered.
Figure 4-35 Zone linkage setup
4.3.3
Building linkage setup
The drop-down selection box is incorporated into the building linkage. The corresponding
options will be displayed only after building information is registered.