Installing the Curtain Rewind Switch
The curtain rewind switch initiates a temporary roll-up of a deployed curtain, allowing
someone to move through the opening. The curtain then unwinds to the fully deployed
position if the smoke detector is still in alarm.
During shipping, the two sides of the switch are banded together and the wire that
connects the switch to the housing is attached to the inside of the housing. When you
are ready to attach the rewind switch, cut the ties that hold the wire and allow the wire
and switch to drop from the housing.
Model 600 Components
°
2 sides of a rewind switch, 1 with a female amp connect and 1 without
°
Kapton
®
tape
Tools/Materials
°
permanent marker
°
measuring tape
°
utility knife
°
zip ties (supplied)
NOTE: Any alteration to a place of public accommodation or a commercial facility shall
be made so as to ensure that, to the maximum extent feasible, the altered portions of the
facility are readily accessible to and usable by individuals with disabilities, including
individuals who use a wheelchair. (Americans with Disabilities Act)
To mount the rewind switch:
1. Mark the center of the curtain
42 inches up from the floor
(see note above).
2. Cut the zip tie holding the
switch.
3. Peel off the backing from the
adhesive on the side of the
switch that is connected to
the wire.
4. On the landing side of the
curtain, while keeping both
the switch and the curtain
FLAT, mount the middle of
the switch over the mark you
created in step 1.
the landing
side of curtain
42”