9
Technical data
Design with operating point 400 V/50 Hz
Operating Instructions – MOVIFIT
®
FC
177
MOVIFIT
®
type
MTF
11A
003-503
MTF
11A
005-503
MTF
11A
007-503
MTF
11A
011-503
MTF
11A
015-503
MTF
11A
022-503
MTF
11A
030-503
MTF
11A
040-503
Size 1
Size 2
Ambient temperature
-25 – +40 °C (P
N
derating: 3 % I
N
per K to max. 60 °C)
Climate class
EN 60721-3-3, class 3K3
Storage temperature
2)
-25 – +85 °C (EN 60721
‑
3
‑
3, class 3K3)
Maximum permitted
vibration and shock
load
According to EN 50178
Overvoltage category
III according to IEC 60664
‑
1 (DIN VDE 0110
‑
1)
Pollution class
2 according to IEC 60664
‑
1 (DIN VDE 0110
‑
1) within the housing
Installation altitude
(see chapter "Electrical
Installation" > "Installa-
tion instructions")
h
h ≤ 1000 m: no derating
h > 1000 m: I
N
reduction by 1% per 100 m
h > 2000 m: V
line
derating by AC 6 V per 100 m
h
max
= 4000 m
Derating for tilted
mounting positions
(see chapter "Mechani-
cal Installation" >
"Mounting position"
S1 operation: I
N
= 100%
S1 op-
eration:
I
N
= 90%
S3 operation: I
N
= 100%
Weight
EBOX "MTF...-....-00" (MOVIFIT
®
FC) size 1: approx. 3.5 kg
EBOX "MTF...-....-00" (MOVIFIT
®
FC) size 2: approx. 5.6 kg
Standard ABOX: approx. 4.5 kg
Hybrid ABOX: approx. 4.8 kg
1) 16 kHz PWM frequency (low-noise):The unit switches to lower cycle frequencies depending on the heat sink temperature and load.
2) If the unit is stored for a long time, connect it to the line voltage for at least 5 minutes every 2 years. Otherwise, the service life of the
unit may be reduced.
21316996/EN – 12/2014