9
Technical data
MOVIFIT® compact inverter
Operating Instructions – MOVIFIT
®
compact
95
MOVIFIT
®
compact type
MBF07B-..
MBF11B-..
MBF15B-..
Installation altitude
h ≤ 1000 m: no reduction
h > 1000 m: I
N
reduction 1% per 100 m
h > 2000 m: U
Mains
reduction AC 6 V per 100 m,
overvoltage class 2 in accordance with
EN 60664-1
h
max
= 4000 m
Mass
4.5 kg
Dimensions
See chapter “Dimension drawing”
Required preventive meas-
ures
Grounding the device
Protection functions
•
Shutdown in the event of overcurrent due to
earth fault, short circuit, or overload
•
Shutdown in the event of overvoltage at the
DC link
•
Shutdown in the event of overtemperature
•
Motor monitoring in accordance with UL
function
1) Connect device to the line voltage for at least 5 minutes every 2 years in the event of extended storage.
Otherwise, the service life of the device may be reduced.
22527060/EN – 08/2017