MOVIFIT® compact error list
Operating Instructions – MOVIFIT
®
compact
88
Code Subcode Meaning
Possible cause
Measure
F 43
0
Internal communication
error
Communication
problem between
internal control
section and
power section.
•
Contact SEW‑EURODRIVE Service.
F 45
o
Initialization error
Current offset
measurement out
of tolerance.
•
Reset the error.
•
If the error persists, contact SEW-
EURODRIVE Service.
17, 20
Initialization error,
power section assignment
Internal power
section not com-
patible
•
Contact SEW‑EURODRIVE Service.
F 50
0, 7
Supply voltage error in in-
ternal power section
•
Contact SEW‑EURODRIVE Service.
F 84
0
Thermal overload of motor
Ambient temper-
ature at motor too
high
•
Lower the ambient temperature at
the motor.
•
Reset the error.
Heat build-up at
the motor
•
Prevent heat build-up at the motor.
•
Reset the error.
Motor load too
high
•
Reduce the load of the motor.
Speed of motor
too slow
•
Increase the speed.
•
Reset the error.
F 94
12
Detected power section
does not correspond to the
configured power section.
When the internal
power section
was replaced, a
different type
than the previous
one was in-
stalled.
•
Contact SEW‑EURODRIVE Service.
F 97
0, 1
Copy error
Error during data
backup with the
MBBG11A oper-
ating panel
•
Repeat the copying process.
•
Load the factory settings and re-
parametrize the device.
F 98
0
CRC calculation via flash
code
-
•
Reset the error.
•
If the error persists, contact SEW-
EURODRIVE Service.
F
196
0
Power section collective
error, error assignment not
possible.
Error detection
aborted or sensor
signal missing.
•
Reset the error.
•
If the error persists, contact SEW-
EURODRIVE Service.
22527060/EN – 08/2017