5
Electrical installation
Power bus connection (line cable)
Operating Instructions – MOVIFIT
®
compact
27
6.
NOTICE!
Penetration by moisture or dust caused by non-permissible cable seal.
Damage to the MOVIFIT
®
compact device.
Only use cable seals that are approved for the diameter of the power supply cable
(→
). Insert the cable seals with the power supply cable in the recesses in
the ABOX.
16938797323
7.
WARNING!
Risk of crushing due to wrong direction of rotation or damage due
to reverse connection of phases. Severe or fatal injuries, irreparable damage to
the device.
Observe the following connection diagram. Prevent short circuits. Insert the con-
ductors of the power supply cable into the cable entries in accordance with the fol-
lowing connection diagram:
L1
N
L2
PE
L3
L1
N
L2
PE
L3
9007202094614795
Con-
ducto
r
Conductor color/conductor marking
According to:
IEC 60757
UL 1277
TC‑ER
UL 62 ST
OOW
L1
Brown
Black or 1
Black
N
Blue
White or gray
–
L2
Black
Black or 2
White
PE
Green/yel-
low
Green/yellow
Green
L3
Gray
Black or 3
Red
22527060/EN – 08/2017