![SEW-Eurodrive INTERBUS UFI11A Manual Download Page 49](http://html.mh-extra.com/html/sew-eurodrive/interbus-ufi11a/interbus-ufi11a_manual_1250336049.webp)
Manual – Fieldbus Interface INTERBUS UFI11A
49
7
Diagnostic LEDs
7
Diagnostic LEDs
The UFI11A INTERBUS interface has 7 diagnostic LEDs.
•
LED "UL" (green) Logic voltage
•
LED "RC" (green) Incoming remote bus OK
•
LED "BA" (green) Bus mode active
•
LED "RD" (yellow) Outgoing remote bus switches off
•
LED "TR" (green) Parameter data exchange via PCP channel
•
LED "SYS-FAULT"(red) for displaying system errors and operating conditions of the
UFI11A
•
LED "USER" (green) for application-specific diagnostics in expert mode
7.1
States of the LEDs UL, RC, BA, TR and RD
LED UL "U-Logic"
(green)
LED RC "Cable
Check" (green)
LED BA "Bus
Active" (green)
LED RD "Remote
Bus Disable"
(red)
Status
Meaning
Remedy
on
Supply voltage of bus electro-
nics is present
-
off
Supply voltage of bus electro-
nics is missing
Check the 24V voltage supply of the UFI11A.
Status
Meaning
Remedy
on
Incoming remote bus connec-
tion is ok
-
off
Incoming remote bus connec-
tion is faulty
Check the incoming remote bus connection.
Status
Meaning
Remedy
on
Data transmission via INTER-
BUS active
-
off
No data transmission; INTER-
BUS has been stopped
Check the incoming remote bus cable. Use the diagnostics
display of the INTERBUS interface module (master) for
additional error localization.
Status
Meaning
Remedy
on
Outgoing remote bus turned off
-
off
Outgoing remote bus not turned off
-
Summary of Contents for INTERBUS UFI11A
Page 1: ...INTERBUS UFI11A Fieldbus Interface Edition 06 2002 Manual 1052 5114 EN ...
Page 2: ......
Page 65: ......
Page 66: ......
Page 67: ......