Manual – Fieldbus Interface INTERBUS UFI11A
29
5
INTERBUS Interface
The PCP channel can be set to 0, 1, 2, or 4 words. At least one word must be set to
enable parameter data to be exchanged. Higher settings increase the transmission
speed. Fig. 8 shows the possible settings for the PCP channel.
Note that if the total of process data and PCP words exceeds 10 words, you must select
a value equal to or greater than your required data length from the following settings:
0 – 10 words set directly, 12 words, 14 words, 16 words, 24 words and 26 words.
A maximum of 3PDs can be assigned to one station on the SBus.
05378AXX
Fig. 22: Possible settings for PCP words