Manual – Fieldbus Interface INTERBUS UFI11A
Installation and Operation with Autosetup
3.5
Starting the inverters
You can operate up to eight inverters on the INTERBUS via one UFI11A. The INTER-
BUS master and the UFI11A will exchange setpoints and actual values of all inverters
connected to the UFI11A in contiguous data packages. It is important for you to know
where a particular inverter is located in the data package (process image). The relation-
ship is shown in the following illustration:
You can enable the inverter by writing the value 0006h in the corresponding control
word. You can enter the speed setpoint in the following word; it is scaled with 0.2 1/min
per digit.
05431AXX
Fig. 6: Data exchange INTERBUS master – UFI11A – inverter