Manual – Fieldbus Interface INTERBUS UFI11A
45
5
INTERBUS Interface
Additional code
The "Additional code" contains all SEW-specific return codes for incorrect parameter
setting of the drive inverters. These codes are sent back to the master as "Error class 8
= Other error." Table 2 lists all possible codes for the additional code.
Special case
"Internal
communication
error"
The return code listed in the following table will be generated in case of a communication
error between option card and inverter system. The PCP service transmitted via fieldbus
may not have been executed and should be repeated. In case this error occurs frequent-
ly, the drive inverter will have to be turned off and on again to start a new initialization.
Add. code
high (hex)
Add. code low
(hex)
Meaning
00
00
No error
00
10
Incorrect parameter index
00
11
Function/parameter not available
00
12
Read access only
00
13
Parameter block is active
00
14
Factory setting is active
00
15
Value too large for parameter
00
16
Value too small for parameter
00
17
No option card available for this function/parameter
00
18
Error in system software
00
19
Parameter access via RS485 process interface on X13 only
00
1A
Parameter access via RS485 diagnostics interface only
00
1B
Limited-access parameter
00
1C
Requires controller inhibit
00
1D
Invalid parameter value
00
1E
Factory setting has been activated
00
1F
Parameter was not saved in EEPROM
00
20
Parameter cannot be changed with enabled output stage
Code (dez)
Meaning
Error class:
6
Access
Error code:
2
Hardware problem
Add. code high:
0
-
Add. code low:
0
-