Manual – Fieldbus Interface INTERBUS UFI11A
INTERBUS Interface
"Download para-
meter block"
object
The "download parameter block" object enables up to 38 drive parameters of the
UFI11A or an inverter connected to the UFI11A to be written at the same time with only
one write service. This object gives you the opportunity to set the parameters of the in-
verter in the startup phase, by calling the write service only once. In general, only a few
parameters vary from application to application so that this parameter block with its max.
38 parameters is sufficient for almost all applications. The user data area is defined as
38 x 6 + 2 bytes = 230 bytes (byte format). The following table shows the structure of
the "download parameter block" object.
The "download parameter block" object is only handled locally on the fieldbus interface
and is defined as in the following table.
Octet
Meaning
Note
0
Address
Target address: 0 or 254 for the UFI11A or SBus address of the
target inverter
1
Number of parameters
1 – 38 parameters
2
Index high
1st parameter
3
Index low
4
Data MSB
5
Data
6
Data
7
Data LSB
8
Index high
2nd parameter
...
...
223
Data LSB
224
Index high
38th parameter
225
Index low
226
Data MSB
227
Data
228
Data
229
Data LSB
Index:
8296
Object code:
7 (simple variable)
Data type index :
10 (octet string)
Length:
230
Local address:
Password:
Access groups:
Access rights:
Write all
Name[16]:
-
Extension length:
-