5
Startup
Startup of "full PLC configuration"
Manual – ECDriveS
®
23
5.2.1
Setting the configuration parameters of the ECC-DFC fieldbus controller
The ECC-DFC fieldbus controllers are configured in the TIA Portal:
1. Open the "General" [1] tab in the TIA Portal.
2. Select the [Module parameters] menu command [2].
ð
Here, you can configure all the settings for the ECC-DFC fieldbus controller.
[1]
[2]
25265833611
[1]
"General" tab
[2]
Module parameters
In contrast to the configuration with ECShell, the configuration parameters in "full PLC
configuration" are written again every time the bus is started up.
5.2.2
Introduction of topology detection
The PROFINET technology detection allows for configuring and monitoring the struc-
ture of the network with the PROFINET IO controller in addition to the PROFINET IO
devices.
The so-called "Physical device" (PDEV) is the starting point for the configuration.
PDEV is a model for the Ethernet interface and can be found in slot0 in the configura-
tion with an "Ethernet interface" subslot and one subslot for each Ethernet port.
The Ethernet ports made visible in this way can be connected to the configuration tool.
The result is an image of the desired Ethernet routing for the plant. This image is
stored in the PROFINET IO controller.
In order to be able to determine the real plant topology, the PROFINET IO devices
must support the so-called LLDP (Link Layer Discovery Protocol). The PROFINET IO
devices exchange information with the neighboring PROFINET IO devices via LLDP.
Each PROFINET IO device cyclically sends information about its own PROFINET
device name and port number via LLDP. The neighboring device receives and stores
this information. A PROFINET IO controller can then read the stored information from
the PROFINET IO devices and so determine the real plant topology.
By comparing the configured topology with the real topology, you can detect any miss-
ing or incorrectly wired PROFINET IO devices and localize them in the plant.
Apart from cabling, you can still determine the transmission characteristics for the
ports. For example, you can set an "Auto-negotiation" port to "100 Mbit full duplex".
The settings will be monitored.