3
Assembly and installation notes
Installation of bus cable
Manual – ECDriveS
®
11
•
Use only connectors with a metal housing or a metalized housing.
•
Connect the shielding in the connector over a wide surface area.
•
Apply the shielding of the bus cable on both ends.
•
Always route the signal and bus cables spatially separated from power cables
(motor leads) and, whenever possible, in separate cable ducts.
•
Use metallic, grounded cable racks in industrial environments.
•
Route the signal cable and the corresponding equipotential bonding close to each
other using the shortest possible route.
•
Avoid using plug connectors to extend bus cables.
•
Route the bus cables closely along existing grounding surfaces.
3.2.2
Ethernet cable with suitable RJ45 connector
INFORMATION
To make it possible to mount the supplied covers of the fieldbus controller, the over-
molding of the Ethernet cables must be no higher than 15 mm and no longer than
45 mm.
15 mm
45 mm
24848592907
The following PROFINET-certified Ethernet cables can be used for the connection
between the PROFINET master and an ECC-DFC fieldbus controller:
Manufac-
turer
Designation
Design
Length in m
Weidmüller
IE-C5D-
S4VG0010A60A60-E
RJ45 IP 20 – RJ45 IP 20
1
IE-C5D-
S4VG0100A60A60-E
RJ45 IP 20 – RJ45 IP 20
10
IE-C5D-
S4VG0050A60XXX-E
RJ45 IP 20 – open end
5
IE-C5D-
S4VG0100A60XXX-E
RJ45 IP 20 – open end
10
IE-C5D-
S4VG0200A60XXX-E
RJ45 IP 20 – open end
20
IE-C5D-
S4VG0500A60XXX-E
RJ45 IP 20 – open end
50
Further lengths are available upon request from Weidmüller.