Configuring a PROFIBUS DP master
Configuration and Startup on the PROFIBUS DP-V1 Fieldbus
Slot 2:
Slots 4 to 18:
Configuration
example
Slot 1: Empty
Slot 2: Param (4 words)
Slot 3: 10 PD
Configuration telegram sent to the MOVI-PLC
®
advanced
DHF41B control card: 0x00
0xC0 0xC87 0x87 0xC0 0xC9 0xC9
Parameter data
Configuration
Meaning / notes
DP configurations
Empty
Reserved
0x00
Param (4words)
MOVILINK
®
parameter channel
configured
0xC0, 0x87, 0x87
Process data
Configuration
Meaning / notes
DP configurations
1 PD
Process data exchange via
1 process data word
0xC0, 0xC0, 0xC0
2 PD
Process data exchange via
2 process data words
0xC0, 0xC1, 0xC1
3 PD
Process data exchange via
3 process data words
0xC0, 0xC2, 0xC2
4 PD
Process data exchange via
4 process data words
0xC0, 0xC3, 0xC3
5 PD
Process data exchange via
5 process data words
0xC0, 0xC4, 0xC4
6 PD
Process data exchange via
6 process data words
0xC0, 0xC5, 0xC5
7 PD
Process data exchange via
7 process data words
0xC0, 0xC6, 0xC6
8 PD
Process data exchange via
8 process data words
0xC0, 0xC7, 0xC7
9 PD
Process data exchange via
9 process data words
0xC0, 0xC8, 0xC8
10 PD
Process data exchange via
10 process data words
0xC0, 0xC9, 0xC9
11 PD
Process data exchange via
11 process data words
0xC0, 0xCA, 0xCA
12 PD
Process data exchange via
12 process data words
0xC0, 0xC7, 0xC7
13 PD
Process data exchange via
13 process data words
0xC0, 0xCC, 0xCC
14 PD
Process data exchange via
14 process data words
0xC0, 0xCD, 0xCD
15 PD
Process data exchange via
15 process data words
0xC0, 0xCE, 0xCE
16 PD
Process data exchange via
16 process data words
0xC0, 0xCF, 0xCF
32 PD
Process data exchange via
32 process data words
0xC0, 0xDF, 0xDF
64 PD
Process data exchange via
64 process data words
0xC0, 0xFF, 0xFF