Manual – MOVI-PLC® advanced DHF41B DeviceNet and PROFIBUS DP-V1 Fieldbus Interfaces
105
12
Communication via Ethernet
Operating MOVITOOLS® MotionStudio
12.5.3 Setting communication parameters for SMLP
SMLP
communication
parameters
The following table describes the communication parameters for SMLP:
To set up communication parameters for communicating via Ethernet, proceed as
follows:
1. If necessary, change the preset communication parameters. Refer to the detailed
description of the communication parameters for SMLP.
Communication parameters of
the simple MOVILINK
®
protocol
Description
Note
Timeout
Waiting time in [ms] that the client
waits for a response from the
server after it has made a
request.
•
Default setting: 1000 ms
•
Increase the value as
required if a delay in
communication is causing
malfunctions.
Broadcast IP address
IP address of the local network
segment
within
which the unit
scan is carried out.
In the default setting, the unit
scan only detects units that are in
the local network segment.
IP address of SMLP server
IP address of the SMLP server or
of other units that are to be
included in the unit scan but are
outside
the local network
segment.
•
Enter the IP address of units
that are to be included in the
unit scan but are
outside
the
local network segment.
Excluded IP address
IP addresses of units that should
not
be included in the unit scan.
Enter the IP address of units that
should
not
be included in the unit
scan. This can be units that are
not ready for communication (for
example because they have not
been started up yet).
TIP
During a unit scan, the system recognizes only units that are in the same (local)
network segment as the PC that is running on MOVITOOLS
®
MotionStudio.
• If you have units that are
OUTSIDE
the local network segment, add the IP
addresses of these units to the list of SMLP servers.