Manual – MOVI-PLC® advanced DHF41B DeviceNet and PROFIBUS DP-V1 Fieldbus Interfaces
5
Project planning examples in RSLogix5000
Project Planning and Startup on the DeviceNet Fieldbus
Only a few additions are necessary for activating write access to a parameter:
• Create the controller tags (see following figure)
• Create a rung for executing the "WriteParameter" command (see following
figure).
For contact, select the tag "WriteParameterStart"
For message control, select the tag "WriteParameter"
• Click on
in the MSG instruction to open the "Message Configuration" window
(see following figure).
Fill the other fields in the following sequence:
– Source Element = WriteParameterRequest.Index
– Source Length = 12
– Destination = WriteParameterResponse.Index
– Class = 7
hex
– Instance = 2
– Attribute = 4
hex
– Service Code = 10
hex