![SEW-Eurodrive DHF41B Manual Download Page 57](http://html.mh-extra.com/html/sew-eurodrive/dhf41b/dhf41b_manual_1250085057.webp)
Manual – MOVI-PLC® advanced DHF41B DeviceNet and PROFIBUS DP-V1 Fieldbus Interfaces
57
9
Configuring a PROFIBUS DP master
Configuration and Startup on the PROFIBUS DP-V1 Fieldbus
4. Enter the I/O or peripheral addresses for the configured data widths in the "I Address"
[1] and "Q Address" [2] columns.
DP configuration
To enable the MOVI-PLC
®
advanced
DHF41B control card to support the type and
amount of input and output data to be transmitted, the DP master on the MOVI-PLC
®
advanced
DHF41B control card must transmit the corresponding DP configuration. The
configuration telegram comprises the DP configurations for slots 1 to 18.
You can:
• Control the MOVI-PLC
®
advanced
DHF41B control card using process data
• Read or write parameters using the parameter channel
The following tables contain additional information on possible DP configurations.
• The "Parameter data/Process data configuration" column displays the name of the
configuration. These names also appear in a selection list in the configuration
software for the DP master.
• The "DP configurations" column shows the configuration data that is sent to the
MOVI-PLC
®
advanced
DHF41B control card when the link to the PROFIBUS DP
system is being established.
Slot 1:
12056AXX
Parameter data
Configuration
Meaning / notes
DP configurations
Empty
Reserved
0x00
0
0
I
Summary of Contents for DHF41B
Page 2: ...SEW EURODRIVE Driving the world ...