Manual – MOVI-PLC® advanced DHF41B DeviceNet and PROFIBUS DP-V1 Fieldbus Interfaces
21
5
Project planning examples in RSLogix5000
Project Planning and Startup on the DeviceNet Fieldbus
5.4
Project planning examples in RSLogix5000
5.4.1
MOVI-PLC
®
advanced DHF41B with 16 process data
1. Set the DIP switches on the DHF41B to do the following:
• Adjust the baud rate to the DeviceNet
• Set the address (MAC-ID) to a value used by no other node
2. Insert MOVI-PLC
®
advanced
DHF41B into the DeviceNet configuration as described
in the chapter "Configuring the PLC and master (DeviceNet scanner)".
3. Set the number of process data words of MOVI-PLC
®
advanced
DHF41B to 16.
4. You can now start integration into the RSLogix project.
To do so, create a controller tag with a user-defined data type to create a simple, data
consistent interface to the inverter’s process data (see following figure).
The description for process input and output data of the controller tag can be made
in accordance with the definition of the process data (PD) in MOVI-PLC
®
advanced
DHF41B.
5. To copy the data of MOVI-PLC
®
advanced
DHF41B to the new data structure, a CPS
command is added at the "MainRoutine" which reads the data from the local IO (see
following figure).
11962AXX
0
0
I