SENSORPROX 100R/PIN120 -
SINGLE DOOR CONTROLLER
8
9. SYSTEM WIRING FOR TYPICAL APPLICATION
9-1
. Power Connection
- Connect (+) wire of DC +12V power to Red wire and Red/White banded wire.
- Connect Power GND (-) wire of DC +12V to Black wire and Black/White banded wire.
9-2
. Door Lock Connection
9-2-1 Connection of
POWER FAIL SAFE: Door Lock
- Connect Door RELAY (NC), Blue/White banded wire to DC +12V (be sure that the existing power
supply has enough capacity to support this accessory or upgrade to a sufficient one.)
- Connect (+) wire of Door Lock to Door RELAY (COM), Grey/Red banded wire.
- Connect (-) wire of Door Lock to Power GND (-) wire.
9-2-2 Connection of
POWER FAIL SECURE: Door Lock
- Connect Door RELAY (COM), Grey/Red banded wire to DC +12V (be sure that the existing power
supply has enough capacity to support this accessory or upgrade to a sufficient one.)
- Connect (+) wire of Door Lock to Door RELAY (NO), White/Red banded wire.
- Connect (-) wire of Door Lock to Power GND (-) wire.