USER MANUAL – ZC-SG
8
The HOT ERROR and the COLD ERROR temperature sends the Emergency Object.
The Object is Read Only.
Digital out logic
Digital out logic=0 the digital output it is normally opened.
Digital out logic=1 the digital output it is normally closed.
Object 0x2104: Execute
The object sends command to the CPU: the supported commands are:
Object 0x2104
COMMAND CODE
DESCRIPTION
0xC2FA
Tare acquisition ready to be saved in EEPROM
(allowed also in RUN)
0xC60C
Full scale/known weight acquisition ready to be
saved in EEPROM
(allowed also in RUN)
0xC1BA
Tare acquisition (on RAM)
(allowed also in RUN)
0xD180
Full scale acquisition (on RAM)
(allowed also in
RUN)
0xBAB0
Save new values on EEPROM
(allowed also in RUN)
Object 0x2105: Execute result
The object is used to know the command execution result (only for special commands).
Object 0x2107: Configuration register 1
The object is used to setup the measure and the digital input/output.
CONFIGURATION REGISTER 1 (Object 0x2107)
SUBINDEX
Description
1
Sample number
2
Mode
3
Cell sensibility
4
Digital out logic
5
Digital out mode
6
Digital IN or OUT selection
Sample NR
The sample number it is the number of sample that enters into the measure. Higher values
implies lower response speed but more stability.