USER MANUAL – ZC-SG
20
3
SET1: cell
sensibilit y
0=±1 mV/V
1=±2 mV/V
2=±4 mV/V
3=±8 mV/V
4=±16 mV/V
5=±32 mV/V
6=±64 mV/V
7= from object
0x2108 sub1
UNSIGNED
8
RW
1
4
SET1: digital out
logic
0=the output is
normally open
1=the output is
normally closed
UNSIGNED
8
RW
0
5
SET1: digital out
operation mode
0=the output is
switched when the
gross_weight >
full_scale
1=the output in
switched when the
weight is stable and
the net weight >
threshold
2=the output is
switched when the
weight is stable
UNSIGNED
8
RW
0
6
SET1: digital in
or out mode
0=digital input mode
1=digital output
mode
UNSIGNED
8
RW
0
0x2108
0
SETUP
Channel
Num ber of
param eters
UNSIGNED
8
RO
10
1
SET2: sense
ratio
Cell sense ratio in
mV/V measure
REAL 32
RW
2.0
2
SET2: cell full
scale
REAL 32
RW
10000.0
3
SET2: known
weight
Known weight [kg,
g, etc…]
REAL 32
RW
10000.0
4
SET2: not used
REAL 32
RO
10000.0
5
SET2: not
used
REAL 32
RO
0.0
6
SET2:
threshold
REAL 32
RW
5000.0
7
SET2: Delta
weight
W eight variation
for the stable
condition
REAL 32
RW
1.0
8
SET2: Delta
tim e
The variation
used for the
stable condition
Delta time
·
100 ms
UNSIGNED
16
RW
1
9
SET2: ADC
speed
27=151.71 Hz
55=74.46 Hz
82=49.95 Hz
109=37.59 Hz
155=50.57 Hz
183=24.82 Hz
210=16.65 Hz
237=12.53 Hz
UNSIGNED
8
RW
82
10
SET2: 30000
points
h ysteresis
0x00=full
resolution
0x80=30000 points
resolution
UNSIGNED
8
RW
0x80