USER MANUAL – ZC-SG
19
0x2002
0
Baudrate
Station Baudrate
(only if dip switch
1,2,3 are OFF)
1=20kbps
2=50kbps
3=125kbps
4=250kbps
5=500kbps
6=800kbps
7=1Mbps
UNSIGNED
8
RW
0x01
0x2003
0
Firm ware
release
UNSIGNED
16
RO
1122
0x2030
0
Device
tem perature/
num ber of
param eters
Max subindex
num ber
UNSIGNED
8
RO
4
1
Internal
tem perature
Station internal
tem perature
[°C/10]
INTEGER
16
RO
0
2
Hi Hi
tem perature
Critical hot
tem perature (all
operations stop)
[°C/10]
INTEGER 16
RO
950
3
Hi
tem perature
W arning for too
hot tem perature
[°C/10]
INTEGER 16
RO
900
4
Low
tem perature
Critical low
tem perature (all
operations stop)
[°C/10]
INTEGER 16
RO
-250
0x2104
0
Execute
Supported
comm ands:
0xC2FA=tare
acquisition (ready for
EEPROM saving)
0xC60C=full scale
acquisition (ready for
EEPROM saving)
0xC1BA=tare
acquisition (RAM)
0xD180=full scale
acquisition (RAM)
0xBAB0=save values
in EEPROM
UNSIGNED
16
RW
0
0x2105
Execute result 0=comm and done
1=command
executed with error
UNSIGNED
16
RW
0
0x2107
0
SETUP 1
channel
Num ber of
param eters
UNSIGNED
8
RO
6
1
SET1: sam ple
num ber
Num ber of
sam ples for filter
calculation
[1..100]
UNSIGNED
8
RW
100
2
SET1: m ode
0=use the factory
calibration
1=use a known
weight
UNSIGNED
8
RW
1