User Manual
R-GWR SERIES
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
www.seneca.it
Doc: MI00568-1-EN
Page 39
ADDRESS
(4x)
OFFSET
ADDRESS
(4x)
REGISTER
SENSOR
DESCRIPTION
W/R
TYPE
41126
1125
DIGITAL INPUTS
31
Status of the
digital inputs
Bit 1 = IN0
Bit 2 = IN1
Bit 3 = IN2
Bit 4 = IN3
RO
UNSIGNED
16 BIT
41127
1126
COUNTER / ANALOG
32
Current counter
value / analogue
input [mV]
RO
UNSIGNED
16 BIT
41128
1127
TEMPERATURE [°Cx10]
32
Temperature
measurement in
[°Cx10]
Example 200 =
20.0°C
RO
SIGNED 16
BIT
41129
1128
HUMIDITY [%x10]
32
Relative humidity
measurement in
[%x10]
Example 500 =
50.0%
RO
UNSIGNED
16 BIT
41130
1129
DIGITAL INPUTS
32
Status of the
digital inputs
Bit 1 = IN0
Bit 2 = IN1
Bit 3 = IN2
Bit 4 = IN3
RO
UNSIGNED
16 BIT