User Manual
R-GWR SERIES
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
www.seneca.it
Doc: MI00568-1-EN
Page 11
The meaning of the other fields is as follows:
DHCP (default: Disabled)
Sets the DHCP client to get an IP address automatically.
STATIC IP (
default: 192.168.90.101
)
Sets the device static address. Careful not to enter devices with the same IP address into the same network.
STATIC IP MASK (default: 255.255.255.0)
Sets the mask for the IP network.
STATIC GATEWAY (default: 192.168.90.1)
Sets the gateway address.
MODBUS TCP-IP PORT (default: 502)
Sets the port for the TCP-IP Modbus server.
BAUDRATE MODBUS RTU (SER) (default: 38400 baud)
Sets the baud rate for the RS485 communication port.
DATA MODBUS RTU (SER) (default: 8 bit)
Sets the number of bits for the RS485 communication port.
PARITY MODBUS RTU (SER) (default: None)
Sets the parity for the RS485 communication port.
STOP BIT MODBUS RTU (SER) (default: 1 bit)
Sets the number of stop bits for the RS485 communication port.
PORT TIMEOUT [ms]
Sets the maximum timeout to receive a complete and valid modbus
packet from the serial port.
IP CHANGE DISCOVERY (default: Disabled)
Allows you to enable or not the IP configuration change from the Seneca Discovery Device software.
SYNC CLOCK UPDATE EVERY (default: Day)
Sets the clock synchronization time from the NTP server.
NTP SERVER 1 ADDRESS
Sets the NTP server from which to synchronize the date/time.