ALARM
Selects whether to activate the radio packet immediate sending mode for inputs IN0 and IN1. It is considered
only for the following operating modes:
INPUT0 = ALARM-RISING EDGE, ALARM-FALLING EDGE
or
WATER SENSOR
INPUT1 = ALARM-REED-RISING EDGE, ALARM-REED-FALLING EDGE
or
WATER SENSOR
LINK TX
Sets the transmission power of the radio sensor, selectable between:
0 dB (minimum power, maximum battery life) to 14 dB (maximum power, minimum battery life)
AUTO allows you to automatically calculate the optimal transmission power.
In AUTO mode the sensor performs the following procedure:
1)
The sensor sets the minimum power (0 dB) and, at each sending, raises this power
2)
When the sensor gets 2 consecutive responses from the gateway it uses this transmission power.
It is therefore possible that there are transmission errors in the initial phase if this mode of operation is used.
The procedure can take from 2 to 5 transmissions to be completed and therefore, based on the sending time
set, it can last several minutes/hours.
To speed up the procedure, it is possible to force communication in the radio sensor by pressing the pairing
button IN3 for at least 5 communications.
To carry out a new procedure it is necessary to follow the following points:
1)
Set a transmission power other than AUTO (for example the maximum power of 14 dB)
2)
Forcing a communication in the radio sensor (pressing the IN3 pairing button)
3)
Set the transmission power back to AUTO
4)
Forcing a communication in the radio sensor (pressing the IN3 pairing button)
At this point the procedure for calculating the optimal transmission power will begin.
FAIL MODE
LAST VALUE = In case of sensor fail (communication timeout) the gateway keeps the last values sent
by the radio sensor
LOAD FAIL VALUE = In case of sensor fail (communication timeout) the gateway loads the fail values
FAIL TIMEOUT [x 30s]
Sets the fail time after which, if there has been no communication, the sensor is considered to be in a fail
state. Sets this time so that it is always greater than the sensor send time (SEND TIME).
FAIL VALUE “CNT0/ANG0”, “TEMP”, “HUMIDITY”, “INPUT0”, “INPUT1”, “INPUT2”, “INPUT3”
Sets the value to load in case of fail in the respective variable