User Manual
R-GWR SERIES
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
www.seneca.it
Doc: MI00568-1-EN
Page 35
ADDRESS
(4x)
OFFSET
ADDRESS
(4x)
REGISTER
SENSOR
DESCRIPTION
W/R
TYPE
41089
1088
HUMIDITY [%x10]
22
Relative humidity
measurement in
[%x10]
Example 500 =
50.0%
RO
UNSIGNED
16 BIT
41090
1089
DIGITAL INPUTS
22
Status of the
digital inputs
Bit 1 = IN0
Bit 2 = IN1
Bit 3 = IN2
Bit 4 = IN3
RO
UNSIGNED
16 BIT
41091
1090
COUNTER / ANALOG
23
Current counter
value / analogue
input [mV]
RO
UNSIGNED
16 BIT
41092
1091
TEMPERATURE [°Cx10]
23
Temperature
measurement in
[°Cx10]
Example 200 =
20.0°C
RO
SIGNED 16
BIT
41093
1092
HUMIDITY [%x10]
23
Relative humidity
measurement in
[%x10]
Example 500 =
50.0%
RO
UNSIGNED
16 BIT
41094
1093
DIGITAL INPUTS
23
Status of the
digital inputs
Bit 1 = IN0
Bit 2 = IN1
Bit 3 = IN2
Bit 4 = IN3
RO
UNSIGNED
16 BIT
41095
1094
COUNTER / ANALOG
24
Current counter
value / analogue
input [mV]
RO
UNSIGNED
16 BIT
41096
1095
TEMPERATURE [°Cx10]
24
Temperature
measurement in
[°Cx10]
Example 200 =
20.0°C
RO
SIGNED 16
BIT
41097
1096
HUMIDITY [%x10]
24
Relative humidity
measurement in
[%x10]
Example 500 =
50.0%
RO
UNSIGNED
16 BIT