STK3-GMV10 Control panel and Pre-wiring
For Hydraulic Elevators
MSTK3-GB
Rev.04
05/02/12
© Sea Systems S.r.l.
Page 78 of 81
306
3
The temperature of the control panel is too high. The temperature has overcome the value
set at the parameter 3.7.1 or it is lower than 3 C°
307
4
Oil temperature is out of range for self-tuning
308
4
The speed changing has not occurred at the top floor. The distance to extreme floor < 300
mm in high speed. (with encoder)
309
4
No recognition of the Encoder during the cab moving
310
1
Double safety intervention (with GEV valve)
311
4
No correct count of the Encoder
312
4
The Power supply has lack for less than 200ms
426
5
The number of magnets detected by the SIM sensor is no coherent with the instant count of
the encoder when the cab is at the 1° floor
427
5
The number of magnets detected by the SIM sensor is no coherent with the instant count of
the encoder when the cab is at the 2° floor
428
5
The number of magnets detected by the SIM sensor is no coherent with the instant count of
the encoder when the cab is at the 3° floor
429
5
The number of magnets detected by the SIM sensor is no coherent with the instant count of
the encoder when the cab is at the 4° floor
430
5
The number of magnets detected by the SIM sensor is no coherent with the instant count of
the encoder when the cab is at the 5° floor
431
5
The number of magnets detected by the SIM sensor is no coherent with the instant count of
the encoder when the cab is at the 6° floor
432
5
The number of magnets detected by the SIM sensor is no coherent with the instant count of
the encoder when the cab is at the 7° floor
433
5
The number of magnets detected by the SIM sensor is no coherent with the instant count of
the encoder when the cab is at the 8° floor
434
5
The number of magnets detected by the SIM sensor is no coherent with the instant count of
the encoder when the cab is at the 9° floor
435
5
The number of magnets detected by the SIM sensor is no coherent with the instant count of
the encoder when the cab is at the 10° floor
436
5
The number of magnets detected by the SIM sensor is no coherent with the instant count of
the encoder when the cab is at the 11° floor
437
5
The number of magnets detected by the SIM sensor is no coherent with the instant count of
the encoder when the cab is at the 12° floor
451
5
The SIM signal has not been detected at the 1° floor. The count of the encoder is correct
452
5
The SIM signal has not been detected at the 2° floor. The count of the encoder is correct
453
5
The SIM signal has not been detected at the 3° floor. The count of the encoder is correct
454
5
The SIM signal has not been detected at the 4° floor. The count of the encoder is correct
455
5
The SIM signal has not been detected at the 5° floor. The count of the encoder is correct
456
5
The SIM signal has not been detected at the 6° floor. The count of the encoder is correct
457
5
The SIM signal has not been detected at the 7° floor. The count of the encoder is correct
458
5
The SIM signal has not been detected at the 8° floor. The count of the encoder is correct
459
5
The SIM signal has not been detected at the 9° floor. The count of the encoder is correct
460
5
The SIM signal has not been detected at the 10° floor. The count of the encoder is correct
461
5
The SIM signal has not been detected at the 11° floor. The count of the encoder is correct
462
5
The SIM signal has not been detected at the 12° floor. The count of the encoder is correct
900
3
The bus channel S1-S2 open or disconnect (used for connection with BC01 board)
901
1
Installation operation mode is selected and the electrical connections are for normal
operation mode (cab button panel connection detected) (see Par.4.1)
999
1
Parameter memory checksum is fault