SEA SYSTEMS
INSTALLATION AND USE
STK3-GMV10 Control panel and Pre-wiring
For Hydraulic Elevators
MSTK3-GB
Rev.04
05/02/12
© Sea Systems S.r.l.
Page 54 of 81
3.3.5 Set-up\Info. Shaft\Speed Changes (with valve GEV and 3010)
.1 Ascent
xxxx mm
Ã
Ä
Speed change distance referred to the nominal ascent speed
(range 300…2000 mm).
See the tab. B.8.4.1 and b.8.4.2
.2 Descent
xxxx mm
Speed change distance referred to the nominal descent speed
(range 300…2000 mm).
See the tab. B.8.4.1 and b.8.4.2
3.3.5 Settings \ Low. Comp.\Speed changes (with valve NGV)
.1 Ascent V0
xxxx mm
Ã
Ä
Speed change distance referred to the nominal ascent speed.
(range 300…2000 mm)
.2 Ascent V1
xxxx mm
Ã
Ä
Speed change distance referred to the intermediate ascent speed.
(range 200…2000 mm)
.3 Descent V0
xxxx mm
Ã
Ä
Speed change distance referred to the nominal descent speed.
(range 300…2000 mm)
.4 Descent V1
xxxx mm
Ã
Ä
Speed change distance referred to the intermediate descent speed.
(range 200…2000 mm)
3.3.6 Settings \Info. Shaft\Door Opening
.1 Enabled
NO
Ã
Ä
Enable advance opening of the door when arriving on floor:
•
NO
•
YES
.2 for floor
xxx mm
Distance from the stopping floor where the advance door opening starts
(range 0…120 mm)
3.3.7 Settings \Info. Shaft\Leveling
.1 Ascent
xxxx mm
Ã
Ä
Up re-leveling distance (range 5…100 mm)
.2 Descent
xxxx mm
Down re-leveling distance (range 5…100 mm)