SEA SYSTEMS
INSTALLATION AND USE
STK3-GMV10 Control panel and Pre-wiring
For Hydraulic Elevators
MSTK3-GB
Rev.04
05/02/12
© Sea Systems S.r.l.
Page 60 of 81
3.8 Settings \Timer
3.8.1 Stopping
Timer
: xx s
Ã
Ä
Stopping time at landing after the doors open (engaged time) (range
3…25s)
It is reset by a command in the car and by the door closing button with
recorded command
3.8.2 Photocell
Stop Timer: x.x s
Ã
Ä
Stopping time at landing after the activation of door photocell during door
closure for a departure. (range 0…25 s)
Star—Delta Start-up
Soft Starter Start-up
SCC Start-up
3.8.3 Star Timer:
x.x s
3.8.3 S. Starter
Timer: x.x s
3.8.3 SCC Timer:
x.x s
start-up time (range 0.2…9.9 s)
Ã
Ä
3.8.4 Return
Timer
15 min.:xx min.
Ã
Ä
Waiting time before the returning to the lowest landing (1…15s)
3.8.5 Door 1
Timer max:xx s
Ã
Ä
Maximum time allowed for the operation of the door prior to the intervention
of the Open/Close limit switch of the 1° operator (range 0…25 s)
3.8.6 Door 2
Timer max:xx s
Maximum time allowed for the operation of the door prior to the intervention
of the Open/Close limit switch of the 2° operator (range 0…25 s)
3.9 Settings \Set
.1 Set?
ESC=NO ENT=YES
ESC: Return to the previous menu
ENT: the functions are automatically linked to the inputs (menu 4.4.1) and to
the outputs (menu 4.4.2) according to the parameters set in the menu 2 and
3
If it is necessary to link manually the inputs and outputs, link the input
functions of the tab. F5 to the menu 4.4.1 and link the output functions of the
tab. F6 to the menu 4.4.2
To reset the inputs and outputs with the default functions, use the menu
4.4.4 or the menu 4.4.5