1. Drill a ½” hole in the inside wall or ceiling where you want the cable to come through.
2. Pull cable through hole so the connector end goes to keypad. Route so there is minimal
cable at the keypad.
INSTALL THE WIRING CABLE
3. Attach the wiring connector to the Keypad.
4. Attach the Keypad to the wall.
5. Do NOT mount the Keypad labels until the system is programmed and tested.
P:\INSTALLATION INST\Access Control\INST-936.vsd 0106 Page 7
CONNECTING THE LOCKING DEVICE
Connect the electric locking device to Terminal Strip “B” as outlined in the Typical Wiring
Diagram (see pg 22). Any 3 conductor, 18 gauge wire can be used to connect the Control
Module to the Locking Device. Included with each system are two MOV’s (metal oxide
varistor). The function of the MOV is to absorb any inductive kickback from the locking
device, protecting the circuit board. The MOV’s have been installed under the relay contact
screws and can be left there for normal “FAIL SECURE” lock operation. For “FAIL SAFE”
locks, move one leg from the “N.O.” screw to the “N.C.” screw (see pg 21-22).
If possible,
install the MOV closer to the electric lock.
For switching voltages higher than 36V, remove
the MOV. To provide proper grounding, connect the 3
rd
wire from the body of the locking
device to the “EARTH” screw on Terminal “A”.
1. Connect the Wiring Cable to Terminal Strip “A” following the color sequence on the circuit
board. (see 936 EntryCheck
™
Diagrams, pg 21)
2. Connect 12 to 24 Volts AC to Terminal Strip “C” to screws marked “12-24V AC IN”. If using
an external AC Adaptor, connect BLUE and BROWN to the 12-24V input screws. Connect
GREEN to the “EARTH” screw on Terminal Strip “A”. Plug adapter into a grounded (three
terminal) receptacle.
3. If connecting DC, make connections to Terminal Strip “B”, “DC IN/OUT” instead of “12-
24V AC IN”.
Be sure polarity is correct.
INSTALLING THE CONTROL MODULE
BATTERY BACKUP
Battery backup is NOT required for User Code retention, however, you may wish to connect
an SDC Power Supply with battery backup to provide operation during a power interruption.
NOTE:
Supplied with the system is a 12-conductor cable designed to connect keypad to
control module. You will also need a 3-conductor cable (not included) to connect the control
module to an electric strike or other locking device(s).
IMPORTANT:
The “EARTH” screw terminal on Terminal Strip “A” should be connected to a
true earth ground for proper system protection and operation.