7.3.3.7
RnS PROGRAMS
This tab groups the parameters related to the Program Cycle (
CFG
>>
PROG
) of the device (see
section):
QuickTu
ne
QuickTune Mobile
Programs tab
•
Program Type:
Allows you to define the type of program to be
used: “Do not use programs”, “Ramp and Soak” or “Ramp and Soak
Program” (see
section).
PARAMETERS OF EACH PROGRAM:
Each type of program has specific parameters.
RAMP AND SOAK
•
Maximum rate of Setpoint evolution:
Allows you to define a maximum Setpoint evolution rate. Range: 0 ~ 100.
•
Dwell time at the Setpoint:
Allows you to define a dwell time at the Setpoint. Range: 0 ~ 9999.
RAMP AND SOAK PROGRAM
•
Time base for programs:
Allows you to define a
time base for the programs you create: “Minutes:Seconds” or “Hours:Minutes”.
•
Type of program resumption in case of power failure:
Allows you to define the type of program resumption in case of power failure:
“Resumes at the beginning of the program”, “Resumes at the beginning of the segment”, “Resumes at the exact point where it
stopped”, or “Resumes with control disabled (
RUN
=
No
)”.
•
Program Number being Edited:
Allows you to define the number of the program to be edited. The controller allows up to a maximum
of 20 programs (see
chapter).
•
Program Tolerance:
Allows you to define the maximum deviation to be allowed between the program PV and SP. If exceeded, the
program is suspended (stops counting time) until the deviation is within the tolerance set in this parameter. If set to 0, the program
progresses regardless of the difference between PV and SP.
•
Program Setpoint 0-9:
Allows you to define a setpoint for the configured program (From Setpoint 1 to Setpoint 9).
•
Segment 1-9 Event:
Allows you to define which alarms are to be triggered during a program segment (From Segment 1 to Segment 9).
Available only for alarms whose parameter
Alarm Function 1-4
(Alarms tab) have been configured with the “Event” function.
•
Segment 1-9 Duration:
Allows you to define the duration of each of the 9 segments of the configured program (From Segment 1 to
Segment 9). Range: 99:59 (in minutes) or 0 to 9999 (in seconds), as configured in the
Program Time Base
parameter.
•
Program Link:
Allows you to create a connection between programs, using the number of the program you want to connect to. At the
end of the running program, any other program can start immediately. If set to 0, it means that there is no connection configured. See
section.
RnS TOOL SECTION:
QuickTune
has the RnS Tool, which facilitates the process of creating Ramps and Soaks programs. To use it, simply click the
icon below:
RnS Tool icon
For more specific information on how this tool works, please refer to the software manual.