40
/57
7.3.2.4
TUNING
This tab allows you to configure the parameters related to the tuning mode:
QuickTu
ne
QuickTune Mobile
Tuning tab
•
Auto-Tuning:
Allows you to define the auto-tuning mode:
“Off”, “Fast tuning”, “Precise tuning”, “Precise and auto-adaptative tuning”,
“New precise and auto-adaptative tuning”, “New precise and auto-adaptative tuning when
RUN
=
YES
” (see
chapter).
•
Proportional Band:
Allows you to define the proportional band. It refers to the
P
value of the PID control mode, as a percentage of
the input type maximum range.
When set to 0.0, determines the ON/OFF control mode
. Range: 0 ~ 500.
•
Integral Rate:
Allows you to define the integral rate. It refers to the
I
value of the PID control mode, in repetitions per minute
(Reset). Available only when the
Proportional Band
parameter is
0. Range: 0 ~ 99.99 (in seconds).
•
Derivative Time:
Allows you to define the derivative time. It refers to the
D
value of the PID control mode, in seconds. Available only when
the
Proportional Band
parameter is
0. Range: 0 ~ 300,0 (in seconds).
•
Control cycle action period:
Allows you to define the PWM cycle value. Available only when the
Proportional Band
parameter is
0. Range: 0,5 ~ 100,0 (in seconds).