It is recommended that you do not turn off the controller or change the SP during this process.
During the tuning process, the TUNE indicator will remain lit in the display (see
section). For PWM or pulse output, the quality of the tuning will also depend on the cycle time set.
If the tuning process does not result in satisfactory control, the table below presents guidelines on how to correct the process behavior:
PARAMETER
VERIFIED PROBLEM
SOLUTION
Proportional
Band
Slow response
Decrease
Great oscillation
Increase
Integral Rate
Slow response
Increase
Great oscillation
Decrease
Derivative Time
Slow response or
instability
Decrease
Great oscillation
Increase
Table 17
–
Manual PID parameter setting