background image

Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail [email protected]

www.schischek.com

E X P L O S I O N P R O O F

Torque motor 

8 Nm  

 

15 Nm  

Torque spring return (F) 

min. 8 Nm  

 

min. 15 Nm

Dimension of external torque 

minimum 2 Nm lower load reduce lifetime  

minimum 5 Nm lower load reduce lifetime

Supply voltage/Frequency 

24...240 VAC/DC, ± 10% , self adaptable, Frequency 50...60 Hz ± 20 %

Dimension 

max. starting currents see table "EL-S" (in acc. with voltage, I 

start 

>> I 

rated

), max. 20 W blocking position, approx. 16 W for heater

Protection class 

class I (grounded)

Angle of rotation and indication 

95°, incl. ~ 5° pre-tention, mechanical value indication

Working direction 

selectable by left/right mounting to the damper/valve shaft

Motor running time 

3 / 15 / 30 / 60 / 120 sec. at 90° selectable on site

Motor running time 3 Sec. 

due to external torque and supply voltage 3 to 4 Sec  at 90° ancle

Motor 

brushless DC Motor  

Spring return (F) 

spring return in the event of loss of power

Spring return running time (F) 

spring return in < 1 sec. at 90°

Safety operations  

min. 1.000 in acc. with construction of damper and ambient, consider minimum load

Response time spring return 

up to 1 sec. after power  failure

Control mode 

On-off 

Thermal circuit 

Additional circuit to connect a passive potential free thermostat as a safety sensor, e.g. type InPro-TT-.. in version ..-BF1

InPro-TT-.. connection 

direct to the actuator with M12 × 1,5 mm fast connection

Integrated aux. switches 

2 aux. switches, switching at 5° and 85° Angle of rotation in types ..-SF1 and ..-BF1

Axle of the actuator 

double squared 12 × 12 mm, direct coupling, 100 % overload protected

Electrical connection 

cable, ~1 m, diameter of wires 0,5 mm²

Diameter of cable 

~ Ø 7,3…9,6 mm acc. to type

Cable gland 

M16 × 1,5 mm standard

Manual override 

manual override only if supply voltage is cut, use delivered socket wrench, slow motion, enough torque/force is required

 

Attention: with manual operation of actuators with spring return danger of injury exists, with release/let go the allen key.  

Integral heater 

integral heater, controlled, for ambient temperature down to -40°C

Housing material 

aluminium die cast housing, painted (optional in stainless steel version AISI 316 Type InMax-...-VAS, amercoat painting type InMax ...-CTS)

Dimensions 

L × W × H = 210 × 95 × 80 mm, for diagramm see extra information “ME-S”

Weight    

~ 3,5 kg Aluminium housing (stainless steel ~ 7 kg)

Ambients 

storage temp. -40…+70°C, working temperature -40…+50°C, humidity in acc. with EN 60335-1

Operation mode at 
runningtime motor 3 sec 

the motor will work in 3 seconds only after 1 minute voltage supply. While open/close-operation (open voltage supply and shut it down) 

 

the motor works only with speed 15 sec./90°

Operation mode at
runningtime motor 15 sec
 

at 15/30/60/120 sec. 100 % ED

Self adjustment 

if you select 3 sec. and 15 sec. mode for motor you need to start the self adjustment mode

Maintenance 

maintenance free, maintenance must be complied with regional standards, rules and regulations 

Wiring diagrams (SB) 

SB 1.4 / 1.5 / 7.5 / 7.6  

 

SB 1.4 / 1.5 / 7.5 / 7.6

Delivery 

1 actuator, 1 m cable, double squared shaft connection 12 × 12 mm, 4 screws M4 × 100, 4 nuts M4, socket wrench for simple manual override

Parameter at delivery 

8 Nm, 30 sec./90°  

 

15 Nm, 30 sec./90°

EMV 

Directive 2004/108/EC

Low voltage 

Directive 2006/95/EC

IP-Protection 

IP66, in acc. with EN 60529

Potential compensation 

external PA-terminal, 4 mm²

Certification 

InMax actuators size S

...-VAS 

above listed types in stainless steel housing AISI 316, parts nickel-plated

...-CTS 

above listed types in Al-housing with amercoat painting, parts nickel-plated

InBox-... 

Terminal boxes

InSwitch 

2 external aux. switches, adjustable

MKK-S 

mounting bracket for terminal boxes type InBox-... direct on actuator

HV-S 

comfortable manual override for InMax actuators size S

Adaptations  various adaptations for dampers/valves on request 
BFH-S 

mounting holder for actuators at fire danger area

InPro-TT-.. 

passive temperature sensor

AR-12-xx 

reduction of square damper connection from 12 mm to 11, 10, ...

InMax-..-.F1

Technical data 

InMax-8-.F1  

 

InMax-15-.F1 

Accessories or special solutions size S

Summary of Contents for InMax Revolution

Page 1: ...0 sec at 90 1 sec at 90 On off 2 contacts 5 85 fire trigger SB 7 5 7 6 InMax 15 F1 15 Nm 24 240 VAC DC 3 15 30 60 120 sec at 90 1 sec at 90 On off SB 1 4 1 5 InMax 15 SF1 15 Nm 24 240 VAC DC 3 15 30 60 120 sec at 90 1 sec at 90 On off 2 contacts 5 85 SB 1 4 1 5 InMax 15 BF1 15 Nm 24 240 VAC DC 3 15 30 60 120 sec at 90 1 sec at 90 On off 2 contacts 5 85 fire trigger SB 7 5 7 6 InMax VAS Type as abo...

Page 2: ...operation of actuators with spring return danger of injury exists with release let go the allen key Integral heater integral heater controlled for ambient temperature down to 40 C Housing material aluminium die cast housing painted optional in stainless steel version AISI 316 Type InMax VAS amercoat painting type InMax CTS Dimensions L W H 210 95 80 mm for diagramm see extra information ME S Weigh...

Page 3: ...0 VAC DC a Attention If you use this type of wiring the heater does not work in case of open contact S T Switch Push button Lamp for adjustment behind the blancking plug 10 position switch S Push button T 3 colour LED PA PA PA PA Example InMax 15 BF1 Requested parameter Torque 15 Nm Running time motor 30 sec 90 Result switch position S 02 See extra information EL S A Self adjustment of Angle of ro...

Page 4: ...t to the factory InMax actuators are equipped with an additional temperature sensor to stop the actuator before reaching this max temperature In this case the failure must be eliminated immediately on site H InPro TT The actuator works only with the temperature sensor type InPro TT Details see extra information ME Details see extra information ME InSwitch is an accessory to InMax actuators size S ...

Page 5: ...ltage Uv V Formula for max cable length L at cable cross section A L A l Uv 18V 0 0714 Formula of needed cable cross section A at a cable length of L A 0 0714 l L Uv 18V The EL S data sheet contains additional information for ExMax RedMax and InMax actuators of the size S for the optimization and simplification in regard to planning installation and initial startup It provides influences of extern...

Page 6: ...wn operations l Attache power supply and turn on l Because of inadmissable operation the actuator drove out of safety relevant reasons into an irreversible condition and must be exchanged Accompanying new installation the ambient temperature has to be reduced accordingly Actuator does not work LED does not lights 01 Acuator does not work LED is red blinking 04 l The actuator has been mounted by te...

Page 7: ...d 12 12 mm 60 incl radius of bend for the cable All InMax actuators are equipped with a 10 position switch a push button and a multicolor LED for calibration These control elements are to be found cable laterally behind the two middle sectioned dummy plugs For operation these must be removed The calibration can be achieved despide lining up tension at the actuator It has to be of great concern tha...

Page 8: ...postion must be selected by turning the actuator 180 Mounting 1 Affix tap hole M4 in accordance with drill template on the damper or to a mounting bracket 2 Adjust drive shaft of the actuator with the socket wrench that the drive stands perpendicular to the damper before pluging actuator on to the damper shaft 3 Plug actuator onto damper shaft and fix diagonally with 2 screws 4 Remove the socket w...

Page 9: ...res which require a special adaption Specification E X P L O S I O N P R O O F Schischek GmbH Germany Mühlsteig 45 Gewerbegebiet Süd 5 90579 Langenzenn Tel 49 0 9101 9081 0 Fax 49 0 9101 9081 77 E Mail info de schischek com InMax extra information ME size S 4 4 Mounting to a butterfly valve Mounting to a ball valve 4 Mounting instructions for InMax actuators size S on butterfly valve and ball valv...

Page 10: ...9 0 9101 9081 77 E Mail info de schischek com InMax extra information ME size S Mounting of terminal boxes type InBox via mounting bracket type MKK S to the actuator accessory 2 2 B A 1 Screw mounting bracket MKK S to the actuator A then screw terminal box to the mounting bracket B Mounting bracket MKK S can be mounted every 90 Terminal box mounted above the actuator Terminal box mounted beside th...

Reviews: