Power supply design

The design of the on-site supply, depends on the selected motor running time and selected

supply voltage. Accompanying values are "about values", since there can be construction

unit dispersions within electronics. The power consumption in the blocking  position is run

time independently with max. 20 W. The power consumption for the heater is betwen 5

and 12 W. The heading is running only if the motor is in idle position! The initial starting

supply voltage required by the actuators power supply unit is around 2,0 A for about 1 Sec.

(Please  consider  this  while  concepting  the  cross  section  ot  the  supply  line)

Dimensioning/Design of the supply line

On long distances between voltage supply and drive, voltage drops occur due to line

resistances. As a consequence with 24 VAC/DC the actuator receives a too low tension

and does not start. In order to prevent this, the cross section of the inlet line is to be

designed/dimensioned accordingly. The accompanying formula allows the calculation of

the necessary line cross section, perhabs provides the maximally permitted conduit length

utilizing  the existing line cross section. Alternatively the secondary voltage can be increased

by selecting a transformer. For calcualtion purposses, following characteristics are essential:

UV = supply voltage in [V]

A = line cross section in [mm²]

L = conduit length in [m]

Factor 0.0714 = drive-specific factor

[Vmm²/m] ( based on the electrical conductivity of electrolytic copper with a  coefficient of

56m/Wmm²)

pannel

length „L“ [m]

terminal box

actuator

line cross section

„A“ [mm²]

voltage

„Uv“ [V]

Formula for max. cable length „L“ at cable

cross section „A“

L = A 

(Uv-18V) : 0,0714

Formula of needed cable cross section

„A“ at a cable length of „L“

A = 0,0714 

L : (Uv-18V)

The „EL-S“ data sheet contains additional information for ExMax,

RedMax and InMax actuators of the size "S", for the optimization

and simplification in regard to planning, installation and initial startup.

It provides influences of external factors in reference to the safe

initiation of the actuators, as well as technical references and problem

solutions (error indication). With the error indication, functions can

be examined and different error/problems can be adjusted locally.

Example: A = 1,5 mm², Uv = 24 V

Lengthof cable L = 126 m

Example: L = 250 m, Uv = 30 V

Cross section of  A = 1,5 mm²

Example:

24 V power supply with wire diameter 1,5 mm² = 126 m

Uv [V]

               Rated current in acc. with motor running time

Voltage

Current

3/7,5s

15s

30s

60s

120s

240 V 

I

nominal

0,5 A

0,1 A

0,1 A

0,1 A

0,1 A

120 V 

I

nominal

0,8 A

0,3 A

0,2 A

0,2 A

0,2 A

48 V 

I

nominal

2,0 A

0,6 A

0,3 A

0,3 A

0,3 A

24 V 

I

nominal

4,7 A

1,3 A

0,7 A

0,6 A

0,5 A

Schischek GmbH 

Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail [email protected]

ExMax-.., RedMax-.., InMax extra information EL – F1

E X P L O S I O N P R O O F

u

Power supply design

u

Design of line cross section 24...48 VAC/DC

u

Use at ambient temperatures down to -20°C / - 40°C

u

Error indication - problem treatment/solution

Power input depending of supply voltage

Dimensioning  of the line cross section with 24…48 VAC/DC supply voltages

F1 – extra information EL-S

For additional mechanical data have a look at extra information „ME“

28
27
26
25
24
23
22
21
20

50       100          150          200         250          300          350         400 L[m]

1 mm²

1,5 mm²

2,5 mm²

4 mm²

www.schischek.com

Summary of Contents for InMax Revolution

Page 1: ...0 sec at 90 1 sec at 90 On off 2 contacts 5 85 fire trigger SB 7 5 7 6 InMax 15 F1 15 Nm 24 240 VAC DC 3 15 30 60 120 sec at 90 1 sec at 90 On off SB 1 4 1 5 InMax 15 SF1 15 Nm 24 240 VAC DC 3 15 30 60 120 sec at 90 1 sec at 90 On off 2 contacts 5 85 SB 1 4 1 5 InMax 15 BF1 15 Nm 24 240 VAC DC 3 15 30 60 120 sec at 90 1 sec at 90 On off 2 contacts 5 85 fire trigger SB 7 5 7 6 InMax VAS Type as abo...

Page 2: ...operation of actuators with spring return danger of injury exists with release let go the allen key Integral heater integral heater controlled for ambient temperature down to 40 C Housing material aluminium die cast housing painted optional in stainless steel version AISI 316 Type InMax VAS amercoat painting type InMax CTS Dimensions L W H 210 95 80 mm for diagramm see extra information ME S Weigh...

Page 3: ...0 VAC DC a Attention If you use this type of wiring the heater does not work in case of open contact S T Switch Push button Lamp for adjustment behind the blancking plug 10 position switch S Push button T 3 colour LED PA PA PA PA Example InMax 15 BF1 Requested parameter Torque 15 Nm Running time motor 30 sec 90 Result switch position S 02 See extra information EL S A Self adjustment of Angle of ro...

Page 4: ...t to the factory InMax actuators are equipped with an additional temperature sensor to stop the actuator before reaching this max temperature In this case the failure must be eliminated immediately on site H InPro TT The actuator works only with the temperature sensor type InPro TT Details see extra information ME Details see extra information ME InSwitch is an accessory to InMax actuators size S ...

Page 5: ...ltage Uv V Formula for max cable length L at cable cross section A L A l Uv 18V 0 0714 Formula of needed cable cross section A at a cable length of L A 0 0714 l L Uv 18V The EL S data sheet contains additional information for ExMax RedMax and InMax actuators of the size S for the optimization and simplification in regard to planning installation and initial startup It provides influences of extern...

Page 6: ...wn operations l Attache power supply and turn on l Because of inadmissable operation the actuator drove out of safety relevant reasons into an irreversible condition and must be exchanged Accompanying new installation the ambient temperature has to be reduced accordingly Actuator does not work LED does not lights 01 Acuator does not work LED is red blinking 04 l The actuator has been mounted by te...

Page 7: ...d 12 12 mm 60 incl radius of bend for the cable All InMax actuators are equipped with a 10 position switch a push button and a multicolor LED for calibration These control elements are to be found cable laterally behind the two middle sectioned dummy plugs For operation these must be removed The calibration can be achieved despide lining up tension at the actuator It has to be of great concern tha...

Page 8: ...postion must be selected by turning the actuator 180 Mounting 1 Affix tap hole M4 in accordance with drill template on the damper or to a mounting bracket 2 Adjust drive shaft of the actuator with the socket wrench that the drive stands perpendicular to the damper before pluging actuator on to the damper shaft 3 Plug actuator onto damper shaft and fix diagonally with 2 screws 4 Remove the socket w...

Page 9: ...res which require a special adaption Specification E X P L O S I O N P R O O F Schischek GmbH Germany Mühlsteig 45 Gewerbegebiet Süd 5 90579 Langenzenn Tel 49 0 9101 9081 0 Fax 49 0 9101 9081 77 E Mail info de schischek com InMax extra information ME size S 4 4 Mounting to a butterfly valve Mounting to a ball valve 4 Mounting instructions for InMax actuators size S on butterfly valve and ball valv...

Page 10: ...9 0 9101 9081 77 E Mail info de schischek com InMax extra information ME size S Mounting of terminal boxes type InBox via mounting bracket type MKK S to the actuator accessory 2 2 B A 1 Screw mounting bracket MKK S to the actuator A then screw terminal box to the mounting bracket B Mounting bracket MKK S can be mounted every 90 Terminal box mounted above the actuator Terminal box mounted beside th...

Reviews: