A. Installation, commissioning, maintenance

The cable of the actuator must be installed in a fixed position and protected against 

mechanical and thermical damage. In acc. with operation InMax actuators are 

maintenance free. Nevertheless maintenace must comply with regional standards, 

rules and regulations.

The actuators must not be opened by the customer. For outdoor installation a protective 

housing against rain, snow and sun should be applied to the actuator, as well as a 

constant supply at terminal 1 and 2 for the integral heater. 
B. Shaft connection, selection of running time, heater

InMax actuators are equipped with a direct coupling double squared shaft connection 

of 12 × 12 mm. The housing of the actuator is axially symmetrically built to select 

open/close direction of the spring return function by left/right mounting.

In acc. to the actuator type 5 different motor running times can be selected on site. The 

integral heater is for ambient temperatures down to -40°C.
C. Working with 3 sec. motor running time

See extra information “EL”.
D. Spring return

Spring return function works if the supply voltage (terminal 1 or 2) is cut or open the wire 

3. In the event of an electrical interruption, the spring returns to its end position.
F. Operation at an ambient temperature below -20°C

See extra information “EL-S”.   
G. Excess temperature

An internal thermostat guarantees the temperature class in the event of failure. If this 

thermostat is working the actuator must be sent to the factory.

InMax actuators are equipped with an additional temperature sensor to stop the 

actuator before reaching this max. temperature. In this case the failure must be 

eliminated immediately on site.
H. InPro-TT-..

The actuator works only with the temperature sensor type InPro-TT-.. 

Details see extra information “ME”.

Details see extra information “ME”.

InSwitch is an accessory to InMax actuators size S, fixing 

directly onto the actuator. InSwitch are aux. switches 

with with 2 potential free contacts, adustable on site. 

For periodic inspection of fire dampers cut of the the supply line (cut off the current of 

the actuator)

The switch contact on InPro-TT-.. is only for test aims of actuators function.

For electrical connection of an InMax actuator.

To adapt the InBox direct to the actuator housing an 

additional accessory type MKK-S is required.

InBox-3P  for InMax-..-F1

InBox-Y/S   for InMax-..-SF1

InBox-BF   for InMax-..-BF1

Important information for installation and operation

Extra information "EL-M" (see additional data sheet)

extra technical information, versions of circuit diagrams and failure indication

Extra information "ME-M" (see additional data sheet)

extra technical information, dimensions, installation instruction and illustration

Safety temperature sensor – InPro-TT-..

The safety thermostat type InPro-TT-.. is passive and 

potential free for use in safe circuits, directly connectable 

to the circuit of the InMax-..-BF1 actuators. The sensor 

switches at an ambient temperature of 72°C and starts 

the fail safe spring return function of the actuator.

Mounting of quarter turn valves

Mounting on air dampers with double squared shaft connection

InSwitch – adaptable external aux. switches 

Important information for routine test

InBox – adaptable terminal box

InMax-..-.F1

Mounting instructions and important information for operation and installation

D.IM-05.02-S-en-F1

04-aug-2011

Summary of Contents for InMax Revolution

Page 1: ...0 sec at 90 1 sec at 90 On off 2 contacts 5 85 fire trigger SB 7 5 7 6 InMax 15 F1 15 Nm 24 240 VAC DC 3 15 30 60 120 sec at 90 1 sec at 90 On off SB 1 4 1 5 InMax 15 SF1 15 Nm 24 240 VAC DC 3 15 30 60 120 sec at 90 1 sec at 90 On off 2 contacts 5 85 SB 1 4 1 5 InMax 15 BF1 15 Nm 24 240 VAC DC 3 15 30 60 120 sec at 90 1 sec at 90 On off 2 contacts 5 85 fire trigger SB 7 5 7 6 InMax VAS Type as abo...

Page 2: ...operation of actuators with spring return danger of injury exists with release let go the allen key Integral heater integral heater controlled for ambient temperature down to 40 C Housing material aluminium die cast housing painted optional in stainless steel version AISI 316 Type InMax VAS amercoat painting type InMax CTS Dimensions L W H 210 95 80 mm for diagramm see extra information ME S Weigh...

Page 3: ...0 VAC DC a Attention If you use this type of wiring the heater does not work in case of open contact S T Switch Push button Lamp for adjustment behind the blancking plug 10 position switch S Push button T 3 colour LED PA PA PA PA Example InMax 15 BF1 Requested parameter Torque 15 Nm Running time motor 30 sec 90 Result switch position S 02 See extra information EL S A Self adjustment of Angle of ro...

Page 4: ...t to the factory InMax actuators are equipped with an additional temperature sensor to stop the actuator before reaching this max temperature In this case the failure must be eliminated immediately on site H InPro TT The actuator works only with the temperature sensor type InPro TT Details see extra information ME Details see extra information ME InSwitch is an accessory to InMax actuators size S ...

Page 5: ...ltage Uv V Formula for max cable length L at cable cross section A L A l Uv 18V 0 0714 Formula of needed cable cross section A at a cable length of L A 0 0714 l L Uv 18V The EL S data sheet contains additional information for ExMax RedMax and InMax actuators of the size S for the optimization and simplification in regard to planning installation and initial startup It provides influences of extern...

Page 6: ...wn operations l Attache power supply and turn on l Because of inadmissable operation the actuator drove out of safety relevant reasons into an irreversible condition and must be exchanged Accompanying new installation the ambient temperature has to be reduced accordingly Actuator does not work LED does not lights 01 Acuator does not work LED is red blinking 04 l The actuator has been mounted by te...

Page 7: ...d 12 12 mm 60 incl radius of bend for the cable All InMax actuators are equipped with a 10 position switch a push button and a multicolor LED for calibration These control elements are to be found cable laterally behind the two middle sectioned dummy plugs For operation these must be removed The calibration can be achieved despide lining up tension at the actuator It has to be of great concern tha...

Page 8: ...postion must be selected by turning the actuator 180 Mounting 1 Affix tap hole M4 in accordance with drill template on the damper or to a mounting bracket 2 Adjust drive shaft of the actuator with the socket wrench that the drive stands perpendicular to the damper before pluging actuator on to the damper shaft 3 Plug actuator onto damper shaft and fix diagonally with 2 screws 4 Remove the socket w...

Page 9: ...res which require a special adaption Specification E X P L O S I O N P R O O F Schischek GmbH Germany Mühlsteig 45 Gewerbegebiet Süd 5 90579 Langenzenn Tel 49 0 9101 9081 0 Fax 49 0 9101 9081 77 E Mail info de schischek com InMax extra information ME size S 4 4 Mounting to a butterfly valve Mounting to a ball valve 4 Mounting instructions for InMax actuators size S on butterfly valve and ball valv...

Page 10: ...9 0 9101 9081 77 E Mail info de schischek com InMax extra information ME size S Mounting of terminal boxes type InBox via mounting bracket type MKK S to the actuator accessory 2 2 B A 1 Screw mounting bracket MKK S to the actuator A then screw terminal box to the mounting bracket B Mounting bracket MKK S can be mounted every 90 Terminal box mounted above the actuator Terminal box mounted beside th...

Reviews: