EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
EasyF-IOM connections | EasyF-I8M connections
Construction subject to change
No return possible
Version: 2017-11-13 | Page 6
EASYF-IOM CONNECTIONS
General:
The EasyF-IOM module is equipped with 4 digital inputs and
potential-free changeover contact outputs, which can be
switched or monitored independently of one another.
To the contact marked with + of the EasyF-IOM module, a 24
V DC voltage is applied and then switched via a suitable
contact. Each completed actuation can then be visualised.
Likewise, the EasyF-IOM module allows up to four different
switching functions to be carried out via the potential-free
outputs. At each output, up to 6 A can be switched at 30 V DC
or 250 V AC.
Cons.
No.
Figure
Description
Terminal /
pin
Terminals for connection to the EasyBus network 230 V AC
1
230V AC/50Hz
Terminal 1
230V AC/50Hz
Terminal 2
Zero conductor
Terminal 3
Zero conductor
Terminal 4
Programming and visualisation
2
7-segment display and
programming key
Terminals of the 4 potential-free inputs
3
Signal feedback input A
Terminal 1
24V DC input A
Terminal 2
Signal feedback input B
Terminal 3
24V DC input B
Terminal 4
Signal feedback input C
Terminal 5
24V DC input C
Terminal 6
Signal feedback input D
Terminal 7
24V DC input D
Terminal 8
Terminals for the 4 changeover outputs
(Max. current 6 A at 230V AC or 24V DC)
4
Centre contact COM output A
Terminal 1
NO contact NO output A
Terminal 2
NC contact NC output A
Terminal 3
Centre contact COM output B
Terminal 4
NO contact NO output B
Terminal 5
NC contact NC output B
Terminal 6
Centre contact COM output C
Terminal 7
NO contact NO output C
Terminal 8
NC contact NC output C
Terminal 9
Centre contact COM output D
Terminal 10
NO contact NO output D
Terminal 11
NC contact NC output D
Terminal 12
EASYF-I8M CONNECTIONS
General:
The EasyF-I8M module is equipped with 8 digital inputs that
can be monitored independently of one another.
To the contact marked with + of the EasyF-I8M module, a 24
V DC voltage is applied, which can be switched via a suitable
contact. Each completed actuation can then be visualised.
The switching/wiring states are visualised via LEDs.
Cons.
No.
Figure Description
Terminal /
pin
Terminals for connection to the EasyBus network 230 V AC
1
230V AC/50Hz
Terminal 1
230V AC/50Hz
Terminal 2
Zero conductor
Terminal 3
Zero conductor
Terminal 4
Programming and visualisation
2
7-segment display and
programming key
Terminals of the 8 potential-free inputs
3
+
4
Signal feedback input A
Terminal 1
24V DC input A
Terminal 2
Signal feedback input B
Terminal 3
24V DC input B
Terminal 4
Signal feedback input C
Terminal 5
24V DC input C
Terminal 6
Signal feedback input D
Terminal 7
24V DC input D
Terminal 8
1
3
4
2
1
3
4
2