EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
EasyF-VDC connections | EasyF-VAC connections
Construction subject to change
No return possible
Version: 2017-11-13 | Page 4
EASYF-VDC CONNECTIONS
General:
The EasyF-VDC module is used for connecting and controlling
two independent steadily regulating
DC drives, for example VAV (Variable Air Volume) or valves.
The two independent analogue 0-10 V inputs can receive the
signal, for example of a CO
2
sensor, a temperature sensor,
etc., and be used, for example, for monitoring the air quality
or the like.
Cons. No.
Figure
Description
Terminal / pin
Terminals for connection to the EasyBus network 230 V AC
1
230V AC/50Hz
Terminal 1
230V AC/50Hz
Terminal 2
Zero conductor
Terminal 3
Zero conductor
Terminal 4
Programming and visualisation
2
7-segment display and
Programming key
Terminals of the analogue inputs
3 + 4
0 to 10V DC input
Terminal 1
24V DC
Terminal 2
Ground (GND)
Terminal 3
Terminals for the motors
5 + 6
0 to 10 V input
effective value
Terminal 1
0 to 10 V output
control signal
Terminal 2
24 V DC
Terminal 3
Ground
Terminal 4
EASYF-VAC CONNECTIONS
General:
The EasyF-VAC module is used for connecting and controlling
two independent steadily regulating
AC drives, for example VAV (Variable Air Volume) or valves.
2 drives can be connected to each EasyF-VDC module.
Cons. No.
Figure
Description
Terminal / pin
Terminals for connection to the EasyBus network 230 V AC
1
230V AC/50Hz
Terminal 1
230V AC/50Hz
Terminal 2
Zero conductor
Terminal 3
Zero conductor
Terminal 4
Visualisation
2
7-segment display
Terminals for the VAV motors
3 + 5
GND (GO)
Terminal 1
24V AC (G)
Terminal 2
0-10V VAV control
signal
Terminal 3
0-10V VAV
effective value
Terminal 4
Parameterisation
4
Programming key
1
3
4
2
5
6
1
3
2
4