EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Programming of EasyS-MV2 |
Construction subject to change
No return possible
Version: 2017-11-13 | Page 10
PROGRAMMING OF EASYS-MV2
The programming is carried out via the programming key on
the upper module plug-in card. The menus and menu settings
are visualised via a 7-segment menu.
Go to the programming mode by pressing the programming
key for a long period (>3s). In this mode, select the
corresponding menu by briefly pressing the key and confirm
by pressing it again (>3s). After that, this menu can be edited.
Status displays of EasyS-MV2
When the master is switched on, it shows its firmware
version.
Number 8 corresponds to the firmware version of EasyBus
2.0.
The numbers from 1 to 4 represent the firmware versions of
the variant EasyBus 1.0
The 01 represents the corresponding firmware version. They
differ from other versions by small alterations and bugfixes
Status displays of EasyBus master:
Display State
of
EasyS-MV2
Meaning
Stop
Master is in standby. No
communication takes place in
EasyBus network.
Run
Once the connection to the PLC
via Modbus is established and the
users are detected, the master
switches automatically to this
state.
Scan
Master collects information
about the die EasyBus users
Fire contact
active
All bus users go to safety position
Time out
No connection to the PLC
Programming of EasyS-MV2
In the Modbus submenu, briefly press the programming key
to select the submenu items
- "o" (positive opening operation of the peripheral devices)
- "S" (scan without automatic addressing)
- "S." (scan with automatic addressing)
- "C" (channel change)
- "b" (Modbus submenu)
and hold down the programming key for a long period (>3s)
to display and adjust the corresponding settings. To confirm
the entry, hold down the programming key (>3s) until the
corresponding parameter has been completely set (max. 3
digits). After that, the 7-segment display goes out briefly, the
master restarts and switches to the status display.
The following section explains the corresponding
programming of the submenus.
Display "C"
Positive opening operation
Scan without self-addressing
Scan with self-addressing
Channel configuration
Status display
0 / 1 / F
Display "o"
Display "S"
Display "S."
Display "b"
Modbus configuration