(2) output word address:
Modbus bit address
( decimal )
Description
Remark
4x128
Channel 0 Setting temperature
Set temperature: the target temperature. Adjust
range is –100.0~+350.0 ºC, the precision is
0.1ºC. Do not write radix point when writing
the temperature, e.g.
Write into 500 when
temperature is 50.0ºC.
4x129
Channel 1 Setting temperature
4x130
Channel 2 Setting temperature
4x131
Channel 3 Setting temperature
4x132
Channel 4 Setting temperature
4x133
Channel 5 Setting temperature
4x134
Channel 0 PID Parameter P
The module PID parameters are modified after
self-study process is completed; if users are
not satisfied with the PID parameters, they can
modify them directly. Parameter Diff means
PID control is functional in the area of set
temperature±Diff, the unit is 0.1ºC, the
defaulted value is 100; if the temperature is
less than set temperature–Diff ( heating action
), PID output is the maximum value; if the
temperature is more than set tempDiff,
the PID output is the minimum value.
4x135
Channel 0 PID Parameter I
4x136
Channel 0 PID Parameter D
4x137
Channel 0 PID Parameter Diff
4x138
Channel 1 PID Parameter P
4x139
Channel 1 PID Parameter I
4x140
Channel 1 PID Parameter D
4x141
Channel 1 PID Parameter Diff
4x142
Channel 2 PID Parameter P
4x143
Channel 2 PID Parameter I
4x144
Channel 2 PID Parameter D
4x145
Channel 2 PID Parameter Diff
4x146
Channel 3 PID Parameter P
4x147
Channel 3 PID Parameter I
4x148
Channel 3 PID Parameter D
4x149
Channel 3 PID Parameter Diff
4x150
Channel 4 PID Parameter P
4x151
Channel 4 PID Parameter I
4x152
Channel 4 PID Parameter D
4x153
Channel 4 PID Parameter Diff
4x154
Channel 5 PID Parameter P
4x155
Channel 5 PID Parameter I
4x156
Channel 5 PID Parameter D
4x157
Channel 5 PID Parameter Diff
4x158
Channel 0 Temperature control period
Control period adjust range is 0.5~200s,
minimum precision is 0.1s. The unit is 0.1s, it
means you need to write 5 while the actual
period is 0.5s.
4x159
Channel 1 Temperature control period
4x160
Channel 2 Temperature control period
4x161
Channel 3 Temperature control period
4x162
Channel 4 Temperature control period
4x163
Channel 5 Temperature control period
4x164
Channel 0 Actual temperature
Actual temperature: the users can set the actual
temperature when they found the actual
temperature is different from the displayed
temperature, the unit is 0.1ºC ( the write
4x165
Channel 1 Actual temperature
4x166
Channel 2 Actual temperature
4x167
Channel 3 Actual temperature