10.4.2
10.4.2
10.4.2
10.4.2 Modbus
Modbus
Modbus
Modbus write
write
write
write bit
bit
bit
bit address
address
address
address
(1) bit address
(2) word address:
4x05
Channel 5 Current temperature
4x06
Channel 0 Output value
Digital quantity
:
0~4095
Display current PID output range
4x07
Channel 1 Output value
4x08
Channel 2 Output value
4x09
Channel 3 Output value
4x10
Channel 4 Output value
4x11
Channel 5 Output value
Modbus address
( decimal )
Description
Remark
0x128
Channel 0 PID Control enable signal
When this signal is set on, the PID
control enable bit of this channel
are opened; the PID control process
is closed when reset these bits. All
channels are closed when the power
is on.
0x129
Channel 1 PID Control enable signal
0x130
Channel 2 PID Control enable signal
0x131
Channel 3 PID Control enable signal
0x132
Channel 4 PID Control enable signal
0x133
Channel 5 PID Control enable signal
0x134
-
0x135
-
0x136
Channel 0 Self-study enable signal
Under the condition of the channel
enable bit is set on, set on the self-
study bit to start self-study; when
the self-study bit is 0, it means the
self-study process end or close.
0x137
Channel 1 Self-study enable signal
0x138
Channel 2 Self-study enable signal
0x139
Channel 3 Self-study enable signal
0x140
Channel 4 Self-study enable signal
0x141
Channel 5 Self-study enable signal
Modbus address
( decimal )
Description
Remark
4x128
Channel 0 Setting temperature
Control
the
target
temperature
value.adjust range is 0~1000ºC.
4x129
Channel 1 Setting temperature
4x130
Channel 2 Setting temperature
4x131
Channel 3 Setting temperature
4x132
Channel 4 Setting temperature
4x133
Channel 5 Setting temperature
4x134
Channel 0 PID parameter P
The module PID parameters are
modified after self-study process is
completed; if users are not satisfied
with the PID parameters, they can
modify them directly. Parameter Dif
4x135
Channel 0 PID parameter I
4x136
Channel 0 PID parameter D
4x137
Channel 0 PID parameter Diff
4x138
Channel 1 PID parameter P