This example realizes the PID control of set value and control the object with digital quantity on
the foundation of communication between PLC and MA-8AD. The operation process are as below:
(1) Hardware connection: connect the RS485 com port A, B of MA-8AD and the PLC
(2) Communication parameters setting: baud rate 19200bps, station number 1.
For MA-8AD: baud rate 19200bps, set DIP switch 1-OFF, 2-OFF;
Station number 1, set DIP switch 1-OFF, 2-OFF, 3-OFF, 4-OFF.
For the PLC: set the com port baud rate to be 19200bps, write into the PLC and restart.
(3) Input range configure: via configure tool Config:
4x174
Channel 6 Control period
Min 0.5s, max 200s
4x175
Channel 7 Control period
Min 0.5s, max 200s
4x176
Channel 0 Modified current value
Change current value
4x177
Channel 1 Modified current value
Change current value
4x178
Channel 2 Modified current value
Change current value
4x179
Channel 3 Modified current value
Change current value
4x180
Channel 4 Modified current value
Change current value
4x181
Channel 5 Modified current value
Change current value
4x182
Channel 6 Modified current value
Change current value
4x183
Channel 7 Modified current value
Change current value
4x184
Channel 0 Self-study output range
0%~100%
4x185
Channel 1 Self-study output range
0%~100%
4x186
Channel 2 Self-study output range
0%~100%
4x187
Channel 3 Self-study output range
0%~100%
4x188
Channel 4 Self-study output range
0%~100%
4x189
Channel 5 Self-study output range
0%~100%
4x190
Channel 6 Self-study output range
0%~100%
4x191
Channel 7 Self-study output range
0%~100%
4x192
Channel 0 Difference value setting
4x193
Channel 1 Difference value setting
4x194
Channel 2 Difference value setting
4x195
Channel 3 Difference value setting
4x196
Channel 4 Difference value setting
4x197
Channel 5 Difference value setting
4x198
Channel 6 Difference value setting
4x199
Channel 7 Difference value setting